EXHIBIT A
SECTION 202 IS AMENDED BY ADDING OR AMENDING DEFINITIONS AS FOLLOWS:
24-HOUR BASIS. The actual time that a person is an occupant within a facility for the purpose of receiving care. It shall not include a facility that is open for 24 hours and is capable of providing care to someone visiting the facility during any segment of the 24 hours. See definitions for Group I occupancies as adopted by Harris County.
ADULT DAY CARE FACILITY. See Institutional Group and I-4 occupancy definitions.
ADVANCED EXTERIOR FIREFIGHTING. Offensive firefighting performed outside of an enclosed structure when the fire is beyond the incipient stage. Advanced exterior firefighting often requires firefighting personnel to contain, control and extinguish exterior fires involving site specific hazards, such as flammable and combustible liquid spills or leaks and electrical substations. Advanced exterior firefighting is usually performed using handlines flowing up to 300 gallons per minute (gpm), master streams or similar devices for the manual application of specialized agents. Thermal protective clothing is required, and the use of self-contained breathing apparatus could be required.
ADVANCED EXTERIOR/INTERIOR STRUCTURAL FIREFIGHTING. Firefighting performed that meets both the definition of Advanced Exterior Firefighting and Interior Structural Firefighting.
ALTERNATE HOUSING FACILITY. A residence in which three or more unrelated parolees reside that is owned by an individual, private entity, a non-profit or faith-based organization, but is not operated by, established by, or contracted with the Texas Department of Criminal Justice.
AMBULATORY CARE FACILITY. Buildings or portions thereof used to provide medical, surgical, psychiatric, nursing or similar care on a less-than-24-hour basis to persons who are rendered incapable of self preservation by the services provided or staff has accepted responsibility for care recipients already incapable. This group may include but not be limited to the following:
Dialysis centers
Sedation Dentistry
Surgery centers
Colonic centers
APPROVED. Acceptable to the fire code official
APPROVED CAPACITY. The maximum approved amount or number of gallons that can be received or contained; cubic contents; volume in cubic ft., or in gallons.
ASSISTED LIVING FACILITY. An establishment that furnishes in one or more facilities, food and shelter to four or more persons who are unrelated to the proprietor of the establishment and provides personal care services or administration of medication by a licensed person or may provide limited skilled nursing services as outlined in the Texas Health and Safety Code chapter 247.
BATTERY. A class of devices which contain materials that convert chemical energy into electrical energy which then can be used as a power source. There are several technologies that utilize a variety of materials and chemistries for the purpose of storing this electro-chemical energy for use when required.
BATTERY TYPES. For the purposes of this code, certain types are defined as follows:
FLOW BATTERY. A type of storage battery that includes chemical components dissolved in two different liquids. Ion exchange, which provides the flow of electrical current, occurs through the membrane while both liquids circulate in their respective spaces. (Includes vanadium redox, zinc-bromine, polysulfide-bromide, and other flowing electrolyte-type technologies).
HYBRID SUPERCAPACITOR BATTERY (Lithium-ion capacitor (LIC). The lithium-ion capacitor (LIC or LiC) is a hybrid type of capacitor classified as a type of supercapacitor. It combines lithium-ion technology and electric double layer capacitor (EDLC) construction. It is called a hybrid because the anode is the same as those used in lithium-ion batteries and the cathode is the same as those used in supercapacitors. Activated carbon is typically used as the cathode. The anode of the LIC consists of carbon material which is often pre-doped with lithium ions.
IRON-AIR AQUEOUS BATTERY. The battery includes iron and air electrodes. Each of the cells are filled with water-based, non-flammable alkaline electrolyte (which functions partially like the anolytes and catholytes of flow batteries battery. The battery does not present the risk of thermal runaway. Like the Ni-Fe battery they are relatively coulombically inefficient on float charge, and thus are usually disconnected from the charge bus when at or nearing full charge.
LEAD-ACID BATTERY. An aqueous storage battery that is comprised of lead electrodes, (lead dioxide is the active material for the positive anode and metallic lead is the active material for the negative cathode), immersed in a solution of water and sulfuric acid electrolyte. Common major classification distinctions (i.e., types) include, vented lead-acid (VLA), and valve-regulated lead-acid (VRLA). The VRLA is further subdivided into two types representing the method in which the electrolyte is immobilized: either gelled (gel cell) or absorbed in finely woven porous fiberglass mat (AGM) separators inside the battery between the electrodes.
LITHIUM-ION BATTERY. A storage battery with lithium ions serving as the charge carriers of the battery. The electrolyte is a polymer mixture of carbonates with flammable organic salt in a liquid form. Lithiated metal or mixed metal oxides (e.g. cobalt [LCO], manganese [LMO], nickel-manganese-cobalt [NMC or NCM], nickel-cobalt-aluminum [NCA] or iron phosphate [LFP]) typically make up the cathode and forms of carbon or graphite (or lithium titanate oxide [LTO]) typically form the anode. Each of these different types of cathodes and anode combinations produce different energy densities, different lifetimes, differing fast charge abilities, and differing safety characteristics, among many other things. The choice of Li-ion chemistry is often driven by whichever of these factors or best mix of factors is/are most important for the application.
LITHIUM-SULFER RECHARGEABLE BATTERY. A storage battery that is similar to the lithium-ion battery except that it has a lithium metal anode in the place of the traditional carbon or graphite anode. A lithium-sulfur battery is a secondary (rechargeable) battery that has lithium metal at the anode, sulfur at the cathode, and the electrolyte is nonaqueous.
NICKEL-CADMIUM (Ni-Cd) BATTERY. An alkaline storage battery in which the positive active material is nickel oxide, the negative electrode contains cadmium, and the electrolyte is a solution of water and potassium hydroxide. They lose less life at high temperatures and have better capacity at low temperatures than most other battery technologies and have a long life if not cycled too much.
NICKEL-HYDROGEN (NiH₂). The cells are a hybrid technology, combining elements from both batteries and fuel cells. The battery differs from a nickel–metal hydride (NiMH) battery by the use of hydrogen in gaseous form The nickel–hydrogen cells utilize the nickel hydroxide electrode from nickel–cadmium cells and a platinum hydrogen electrode from fuel cell technology to create a chemistry without the
issues and limitations inherent with the cadmium electrode. The cell is contained within a hermetically sealed pressure vessel that envelopes the electrodes and accommodates the pressurized hydrogen.
NICKEL IRON (Ni-Fe). The battery has nickel (III) oxide-hydroxide positive plates and iron negative plates, with an electrolyte of potassium hydroxide. The active materials are held in nickel-plated steel tubes or perforated pockets. Nickel-iron batteries do not cause spill concerns since there is no acid in the component. They are capable of tens of thousands of cycles and have calendar lifetimes of well over 50 years. However, they are highly coulombically inefficient (with the inefficiency coming from high percentages of water electrolysis from the charging current) when at or near full state-of-charge (SOC). As such, they are usually equipped with catalytic recombiner vents and automatic watering systems.
NICKEL-METAL HYDRIDE (Ni-MH). An alkaline storage battery in which the positive active material is nickel oxide, the negative electrode is an intermetallic compound, and the electrolyte is usually potassium hydroxide solution in water.
NICKEL-ZINC (Ni-Zn). A battery that is chemically similar to the nickel-metal hydride battery. Nickel and zinc have low toxicity, the battery is non-flammable and presents no threat to the environment. The Ni-Zn battery uses an alkaline electrolyte (potassium hydroxide, KOH) and zinc acts as the negative electrode while nickel hydroxide is the positive electrode.
SODIUM NICKEL CHLORIDE (NaNiCl). This battery is a member of the ‘high temperature’ family, which works at typical temperature scope of 270°C–350°C. Its cell contains sodium and nickel chloride electrodes, isolated by a beta-alumina electrolyte, which can conduct sodium particles yet not electrons. This chemistry is much safer than most battery chemistries with far fewer toxic materials involved in its production, but it does not have the cycling ability or energy density of most of the Li-ion chemistries
ZINC-AIR AQUEOUS BATTERY. A zinc-air battery contains a zinc electrode and porous air electrode separated by a membrane and an aqueous alkaline electrolyte that is used in a manner similar to the catholytes and anolytes of a flow battery. The cathode is a bi-functional air electrode which features one or more catalysts that can perform the oxygen reduction reaction (ORR) during discharging and the oxygen evolution reaction (OER) during charging.
ZINC BROMIDE. In zinc bromide batteries, the cathode is made using zinc instead of lithium. The electrolyte is water-based and, therefore, does not pose a fire risk.
ZINC MANGANESE DIOXIDE (Zn-MnO₂). The battery features a Zinc (Zn) anode and a dioxide (MnO₂) cathode with a strongly basic electrolyte (typically potassium hydroxide, KOH), The battery does not present environmental hazards and is EPA-certified for landfill disposal in the United States, and the aqueous electrolyte is non-flammable.
BATTERY-POWERED APPLIANCE. A device or apparatus with an electric motor powered by a battery.
BATTERY-POWERED MICROMOBILITY DEVICES. Products or equipment that include motorized bicycles, motorized scooters and other personal mobility devices intended for one or more riders powered by a lithium-ion or lithium metal battery. The term does not include automobiles and trucks built to DOT requirements.
BATTERY-POWERED INDUSTRIAL EQUIPMENT. A motorized hand truck, floor scrubber, buffer or similar device with an electric motor powered by a battery and intended to be personally driven or guided.
BATTERY-POWERED INDUSTRIAL TRUCK. A forklift, tractor, platform lift truck or similar apparatus with an electric motor powered by a battery.
BATTERY-POWERED AUTOMATED MOBILE PLATFORMS (AMPs). A device with an electric motor powered by a battery that provides an automated function involving lifting, carrying, product picking, towing or similar operations. These devices may also be capable of automatous movement including operating, moving and completing automated functions independently, without direct human guidance or control.
BATTERY POWERED ROBOTIC EQUIPMENT. A machine or device with an electric motor powered by a battery and capable of automatically carrying out a complex series of actions using computer programing. This equipment may be permanently mounted or capable of autonomous movement where they have the means to determine path selection by processing data from sensors, powered by a battery.
BOARDING HOME. A facility that furnishes, in one or more buildings, lodging to three or more persons with disabilities or elderly persons who are unrelated to the owner of the establishment by blood or marriage and provides community meals, light housework, meal preparation, transportation, grocery shopping, money management, laundry services, or assistance with self-administration of medications but does not provide personal care services.
CERTIFICATE OF EXEMPTION. A Certificate of Exemption is awarded to industrial facilities that have a recognized Fire Brigade that meets all applicable Occupational Safety and Health Administration standards (OSHA) 1910. A Certificate of Exemption exempts a facility from fire code regulations affecting or relating to structures, processes, premises, and safeguards relating to construction and operational permits. This exemption does not extend to any other federal, state, or local requirements, nor does the exemption extend to the independent authority of the Fire Marshal to conduct fire and life safety inspections pursuant to Texas Local Government Code 352.
CERTIFICATE OF INSPECTION (COI) — A formal document issued by the Harris County Fire Marshal’s office verifying that a building, structure, system, or operation has been inspected and found to be in compliance with the applicable requirements of the International Fire Code (IFC), Harris County Fire Code, and referenced standards. The certificate confirms that all fire and life safety features are installed, maintained, and functioning as intended at the time of inspection.
CHILD DAY CARE FACILITY. Buildings and structures or portions thereof occupied by more than five children older than 2 ½ years of age for educational, supervision, or personal care services for less than 24 hours are considered a Group E occupancy. If the facility is operated and occupied for the purpose of 24-hour care, it shall be considered a Group I-4 occupancy.
CRITICAL FACILITIES. Those facilities essential to the preservation of life and property, including, but not limited to, type E occupancies of permanent construction and occupant load greater than 1000, nursing homes, assisted living homes, hospitals, police, fire and emergency response installations, and facilities used for the storage of critical records.
DEDICATED FUNCTION FIRE ALARM CONTROL UNIT. A protected premises fire alarm control unit intended to provide operation of a specifically identified fire safety function, such as an elevator recall control and supervisory control unit, only or any system deemed necessary by the Authority Having Jurisdiction.
ELECTRIC VEHICLE CHARGING STATION. One or more vehicle spaces served by an electric vehicle charging system.
ELECTROCHEMICAL DOUBLE LAYER CAPACITORS (EDLCs). These devices are usually built up from an electrolyte, a separator, and two carbon-based electrodes. Also referred to as supercapacitors, they store energy using either ion adsorption (electrochemical double layer capacitors) or fast surface redox reactions (pseudo-capacitors). They are commonly also called “supercapacitors” or the trademarked “ultracapacitor™” because they store orders of magnitude more power and energy for the same unit mass
or volume as a traditional electrolytic capacitor. They can release power and accept charge much faster than batteries for the same footprint, but store much less energy.
FIRE ALARM CONTROL UNIT REPLACEMENT. Any maintenance to an existing fire alarm control unit that involves replacement or upgrade that requires a new installation tag and certification.
FIRE CODE OFFICIAL. The fire code official shall be the person appointed by Commissioners Court as the County Fire Marshal or the employee(s) designated by the County Fire Marshal to perform a task required by this code. The Fire Marshal shall have enforcement authority for this code and shall conduct all required inspections for compliance with this code.
FIRE BRIGADE. Means an organized group of employees who are knowledgeable, trained, and skilled in at least basic firefighting operations. A fire brigade shall be an assembly that meets the requirements of the Occupational Safety and Health Administration standards (OSHA) 1910.
FOSTER GROUP HOME. A child-care facility that provides care for 7 to 12 children on a 24-hour basis.
FOSTER HOME. A child-care facility that provides care for not more than six children on a 24-hour basis.
GENERAL RESIDENTIAL OPERATION. A child-care facility that provides care for more than 7 children for 24 hours a day, including facilities known as children’s homes, halfway houses, residential treatment centers, emergency shelters, and therapeutic camps.
GROUP HOME. An establishment in which three or more individuals who are unrelated to the owner or operator of the establishment resides and provides residential care services to residents; and that receives payment or other compensation from a local, state, or federal government entity for providing
residential care services. This definition does not include:
Home and Community Support Services as defined by Texas Health and Safety Code 142
Convalescent and Nursing Facilities and Related Institutions required to be licensed by Texas and Safety Code 242
Assisted Living Facilities required to be licensed by Texas Health and Safety Code 247
Intermediate Care Facilities for Individuals with an Intellectual Disability required to be licensed by Texas Health and Safety Code 252
Persons that are exempt from licensing under Texas Health and Safety Code Sections 143.003 (a) (19), 242.003 (3), or 247.004 (4).
Hotels
Retirement Community
Monastery or Convent
Child-care Facility
Family Violence Shelter
Sorority or Fraternity House or other Dormitory Associated with an Institution of Higher Education
INCIPIENT FIREFIGHTING. Firefighting performed inside or outside of an enclosed structure or building when the fire has not progressed beyond incipient stage. The incipient stage refers to the severity of a fire where the progression is in the early stage and has not developed beyond that which can be extinguished using portable fire extinguishers or handlines flowing up to 125 gallons per minute (gpm). A fire is considered to be beyond the incipient stage when the use of thermal protective clothing or self-contained breathing apparatus is required, or a Fire Brigade member is required to crawl on the ground or floor to stay below smoke and heat.
INDUSTRIAL FACILITY. Means any land and any building or other improvement thereon, which shall be maintained and utilized for the mechanical or chemical transformation of organic or inorganic substances into new products, characteristically using power-driven machines and materials handling equipment.
INTERIOR STRUCTURAL FIREFIGHTING. The physical activity of fire suppression, rescue, or both, inside of buildings or enclosed structures, which are involved in a fire situation beyond the incipient stage.
LODGING HOUSE. A one-family dwelling that furnishes lodging, for payment, to three or more persons who are unrelated to the owner of the establishment by blood or marriage and one or more of the occupants are primarily permanent in nature. The term lodging house shall include the following:
Emergency Shelters, Halfway Houses, Flophouses, and Alternative Living Facilities, however, the term shall not include a boarding homes, hotels, motels, bed and breakfast facilities, or single-family residential building, condominium, or townhouse that is owner-occupied for at least three months of the year.
MICROMOBILITY CHARGING EQUIPMENT. An electrical device intended for recharging batteries utilized in battery-powered micromobility devices. This equipment is intended to charge multiple battery-powered micromobility devices simultaneously.
MID-RISE BUILDING. A building with an occupied floor located more than 2 stories and less than 75 feet (22 860 mm) above the lowest level of fire department vehicle access.
MOBILE FOOD VENDOR VEHICLE. Vehicles, trailers, and push carts which are used for the preparation, serving or sales of consumable items also know as Mobile Food Units (MFUs).
MOBILE FOOD VENDOR VEHICLE PARK. A property set up with the intent to operate five or more mobile food vendor vehicles and could include buildings, restrooms, common dining areas or other supporting buildings or structures.
ASSEMBLY GROUP A-3. Assembly uses intended for worship, recreation or amusement and other assembly uses not classified elsewhere in Group A, including, but not limited to:
Amusement arcades
Art galleries
Bowling alleys
Community halls
Courtrooms
Dance halls (not including food or drink consumption)
Exhibition halls
Funeral parlors
Greenhouses with public access for the conservation and exhibition of plants
Gymnasiums (without spectator seating)
Indoor swimming pools (without spectator seating)
Indoor tennis courts (without spectator seating)
Lecture halls
Libraries
Martial Arts/Dance Studios/Fitness
Museums
Places of religious worship
Pool and billiard parlors
Waiting areas in transportation terminals
INSTITUTIONAL GROUP I-1. Institutional Group I-1 occupancy shall include buildings, structures or portions thereof for more than 16 persons, excluding staff, who reside on a 24-hour basis in a supervised environment and receive custodial care. Buildings of Group I-1 shall be classified as one of the occupancy conditions indicated below and shall comply with Section 420 of the International Building Code. This group shall include, but not be limited to, the following:
Alcohol and drug centers
Assisted living facilities
Congregate care facilities
Convalescent facilities
Group homes
General residential operation
Halfway houses
Residential board and care
Social rehabilitation facilities
Occupancy Conditions. Buildings of Group I-1 shall be classified as one of the following occupancy conditions and shall comply with Section 407 of the International Building Code:
Condition 1. This occupancy condition shall include buildings in which all persons receiving custodial care who, without any assistance, are capable of responding to an emergency situation to complete building evacuation.
Condition 2. This occupancy condition shall include buildings in which there are any persons receiving custodial care who require limited verbal or physical assistance while responding to an emergency situation to complete building evacuation.
INSTITUTIONAL GROUP I-2. Institutional Group I-2 occupancy shall include buildings and structures used for medical care on a 24-hour basis for more than five persons who are not capable of self-preservation, and not otherwise classified as a This group shall include, but not be limited to, the following:
Foster care facilities
Detoxification facilities
Hospitals
Nursing homes
Psychiatric hospital
Child and Adult day care facilities, operated on a 24-hour basis
Occupancy Conditions. Buildings of Group I-2 shall be classified as one of the following occupancy conditions and shall comply with Section 407 of the International Building Code:
Condition 1. This occupancy condition shall include facilities that provide nursing and medical care but do not provide emergency care, surgery, obstetrics, or in-patient stabilization units for psychiatric or detoxification, including, but not limited to, nursing homes and foster care facilities.
Condition 2. This occupancy condition shall include facilities that provide nursing and medical care and could provide emergency care, surgery, obstetrics, or inpatient stabilization units for psychiatric or detoxification, including, but not limited to, hospitals.
RESIDENTIAL GROUP R-3. Residential Group R-3 occupancies where the occupants are primarily permanent in nature and not classified as Group R-1, R-2, R-4 or I, including:
Buildings that do not contain more than two dwelling units
Community Homes in compliance with Human Resource Code Chapter 123
Congregate living facilities (non-transient) with 16 or fewer occupants
Convents
Dormitories
Fraternities and sororities
Monasteries
Newly Constructed and/or Substantial Improved Boarding and Lodging houses shall comply with the Harris County Fire Code.
Conversion of an existing single-family dwelling into a Boarding or Lodging house.
Lodging houses (transient) with five or fewer guestrooms and 10 or fewer occupants shall be classified as a single-family dwelling for the purpose of this code and comply with all of the following:
Structures not complying with all items listed or determined by the County Engineer or Fire Code Official not approvable shall be classified as new construction or substantial improvement per the Harris County Fire Code.
Boarding Houses in compliance with Chapter 260 of the Health & Safety Code shall be classified as a single-family dwelling for the purpose of this code and comply with all of the following:
Structures not complying with all items listed or determined by the County Engineer or Fire Code Official not approvable shall be classified as new construction or substantial improvement per the Harris County Fire Code.
PERSONAL CARE SERVICE. Assistance with feeding, dressing, moving, bathing, or other personal needs or maintenance, or general supervision or oversight of the physical and mental well-being of a person who needs assistance to maintain a private and independent residence in an assisted living facility or who needs assistance to manage the person’s personal life, regardless of whether a guardian has been appointed for the person.
PREMISES. A building together with its land and outbuildings, or open land occupied by a business or open for public use regardless of the connection with a business.
READILY ACCESSIBLE. Accessible without any special tools, key, knowledge or equipment to operate.
RECOGNIZED FIRE BRIGADE. An approved Facility Fire Brigade which may be provided in several ways, including the following:
or assigned employees of the facility.
facility has a contract with the tenant facility to provide emergency response services.
emergency response team. In these cases, the Brigade is a combination of Facilities located
inside a host facility or located adjacent and functioning as one Fire Brigade.
RESIDENTIAL CARE SERVICES. Shelter, protection, meals, health care, mobility assistance, and personal care services, including bathing, dressing, and eating.
SINGLE-FAMILY DWELLING. Single family residential shall mean the use of a lot with one building designed for and containing not more than two separate units with facilities for living, sleeping, cooking, and eating therein. A lot upon which is located a free-standing building containing one dwelling unit and a detached secondary dwelling unit of not more than 900 square feet also shall be considered single family residential. A building that contains one dwelling unit on one lot that is connected by a party wall to another building containing one dwelling unit on an adjacent lot shall be single family residential.
SPECIAL EVENT. Any organized, temporary event with an estimated number of participants and spectators of 100 or more people set up outdoors in a parking lot, side of the roadway, open land, or involves using a building for an assembly of 50 or more people in a building not equipped or intended to be utilized for this purpose.
START OF CONSTRUCTION. Construction begins on the date that ground is broken for a building, or if no ground is broken, on the date that:
STRUCTURE. Something built or constructed to support or shelter any occupancy.
SUBSTANTIAL IMPROVEMENT. A “Substantial Improvement” is
TEMPORARY. Any construction of a building or structure, tent or membrane structures, or any planned event which will be in operation for no more than 180 days.
TRAINING. The process of making proficient through instruction and hands-on practice in the operation of equipment, including respiratory protection equipment, that is expected to be used and in the performance of assigned duties.
UNINCORPORATED AREA. Unincorporated Area means the area in Harris County, Texas, which is not within an incorporated area of a city, town, and village or within 2,500 feet of the centerline of the Houston Ship Channel.
SECTION 308.1.4.1 IS ADDED TO READ AS FOLLOWS:
308.1.4.1 New and existing apartments and multi-tenant housing. Charcoal burners, LP-gas cooking appliances, open flame cooking devices, gas or fuel fired heaters or any other carbon monoxide producing devices shall not be stored or used in a new or existing Group R2 apartment buildings or multi-tenant housing, including the balcony, patio or within 10 feet of these occupancies.
SECTION 313.2 IS AMENDED TO READ AS FOLLOWS:
313.2 Group R occupancies. Equipment such as vehicles, portable generators, lawn-care equipment and portable cooking appliances powered by flammable liquids, Class II combustible liquids or compressed flammable gases shall not be stored or operated within the living space, balconies or patios, or within 10 feet of Group R buildings.
Exception: Storage within an attached garage complying with this code.
SECTION 319.1 IS AMENDED TO READ AS FOLLOWS:
319.1 General. Mobile food vendor vehicles and mobile food units (MFUs) shall comply with this section.
SECTION 319 IS AMENDED BY ADDING THE FOLLOWING SECTIONS:
319.1.1 Location. Mobile food vendor vehicles used on a property shall comply with the following:
319.1.2 Labeling. All mobile food vendor vehicles shall display signs and stickers as follows:
319.1.3 Egress. All egress pathways in the mobile food vendor vehicle shall provide a minimum clear opening width of 28 inches.
319.1.3.1 Unobstructed egress. The doors in the egress pathway must provide unobstructed egress from the inside and shall not be lockable from the outside with a padlock or other such locking device.
Exception: The padlock or other such locking device is locked in the open position while in operation.
319.8.2.1 Gas systems. Where LP-gas or CNG cylinders are obstructed from view by an enclosure or any other obstruction, a label shall be posted with the words “LP-Gas,” “PROPANE” or similar verbiage on the exterior of the enclosure.
319.8.2.2 Gas storage. LP-gas and CNG containers shall not be installed or stored within the interior of the mobile food vendor vehicle.
319.8.5.1 No smoking. Smoking is prohibited within 10 feet of a mobile food vendor vehicle.
319.10.4 Maintenance. The mobile food vendor vehicle shall be stable in construction and may not be damaged in a way that it could cause a hazard to people or property.
319.11 Electrical. All electrical components shall be in compliance with Section 603 and NFPA 70.
319.12 Solid fuel cooking. All solid-fuel cooking appliances and operations shall be in accordance with NFPA 96, current addition.
319.12.1 Solid fuel storage. Mobile food vendor vehicles may only store up to one day’s supply of solid fuel.
SECTION 322 IS ADDED TO READ AS FOLLOWS:
SECTION 322
BATTERY STORAGE
322.1 General. The storage of batteries shall comply with Section 322.
Exceptions:
322.1.1 Lithium-ion and lithium metal batteries. The storage of Lithium-ion and lithium metal batteries shall comply with Sections 322.2 through 322.4.3.3.
322.1.2 Other battery types. Batteries in storage, other than Lithium-Ion or Lithium metal batteries, shall comply with 322.5 through 322.5.6.
322.2 Permits. Permits shall be required for an accumulation of more than 15 cubic feet (0.42 m³) of lithium-ion and lithium metal batteries, other than batteries listed in the exceptions to Section 322.1, as set forth in Section 105.5.58.
322.3 Fire safety plan. A fire safety plan shall be provided in accordance with Section 403.10.6. In addition, the fire safety plan shall include emergency response actions to be taken upon detection of a fire or possible fire involving lithium-ion or lithium metal battery storage.
322.4 Storage requirements. Lithium-ion and lithium metal batteries shall be stored in accordance with Section 322.4.1. 322.4.2 or 322.4.3, as applicable.
322.4.1 Limited indoor storage in containers. A maximum volume of 15 cubic feet (0.42 m³) of lithium-ion or lithium metal batteries per fire area shall be permitted where stored in accordance with any of the methods provided in Sections 322.4.1.1 through 322.4.1.3.
322.4.1.1 Used or unwanted battery collection. Areas where used or unwanted lithium-ion or lithium metal batteries are collected from the public or employees shall comply with all of the following:
322.4.1.2 Waste storage. Waste batteries that are packaged in accordance with DOTn shipping requirements.
322.4.1.3 Miscellaneous storage. Limited storage of lithium-ion or lithium metal batteries, other than collection of used or unwanted batteries, or waste storage, shall comply with any of the following:
322.4.2 Indoor storage areas. Indoor storage areas for lithium-ion and lithium metal batteries, other than those complying with Section 320.4.1, shall comply with Sections 322.4.2.1 through 322.4.2.6.
322.4.2.1 Technical opinion and report. A technical opinion and report complying with Section 104.8.2 shall be prepared to evaluate the fire and explosion risks associated with the indoor storage area and to make recommendations for fire and explosion protection. The report shall be submitted to the fire code official and shall require the fire code official’s approval prior to issuance of a permit. In addition to the requirements of Section 104.8.2, the technical opinion and report shall specifically evaluate the following:
322.4.2.2 Construction requirements. Where indoor storage areas for lithium-ion and lithium metal batteries are located in a building with other uses, battery storage areas shall be separated from the remainder of the building by 2-hour rated fire barriers or horizontal assemblies. Fire barriers shall be constructed in accordance with Section 707 of the International Building Code, and horizontal assemblies shall be constructed in accordance with Section 711 of the International Building Code.
Exceptions:
322.4.2.3 Fire protection systems. Indoor storage areas for lithium-ion and lithium metal batteries shall be protected by an automatic sprinkler system complying with Section 903.3.1.1 or an approved alternative fire-extinguishing system.
322.4.2.4 Fire alarm systems. Indoor storage areas for lithium-ion and lithium metal batteries shall be provided with an approved automatic fire detection and alarm system complying with Section 907. The fire detection system shall use air-aspirating smoke detection, radiant energy-sensing fire detection or both.
322.4.2.5 Explosion control. Where the approved technical opinion and report required by Section 322.4.2.1 recommends explosion control, explosion control complying with Section 911 shall be provided.
322.4.2.6 Reduced requirements for storage of partially charged batteries. Indoor storage areas for lithium-ion and lithium metal batteries with a demonstrated state of charge not exceeding 30 percent shall not be required to comply with Section 322.4.2.1, 322.4.2.2 and 322.4.2.5, provided that procedures for limiting and verifying that the state of charge will not exceed 30 percent have been approved.
322.4.3 Outdoor storage. Outdoor storage of lithium-ion or lithium metal batteries shall comply with Sections 322.4.3.1 through 322.4.3.6.
322.4.3.1 Technical opinion and report. A technical opinion and report complying with Section 104.8.2 shall be prepared to evaluate the fire and explosion risks associated with outdoor storage of lithium-ion and lithium metal batteries and to make recommendations for fire and explosion protection. The report shall be submitted to the fire code official and shall require the fire code official’s approval. In addition to the requirements of Section 104.8.2, the technical opinion and report shall evaluate all of the following:
322.4.3.2 Distance from storage to exposures. Outdoor storage of lithium-ion or lithium metal batteries shall comply with one of the following:
322.4.3.3 Storage area size limits and separation. Outdoor storage piles for lithium-ion or lithium metal batteries shall not exceed 900 square feet (83.6 m²). The height of battery storage in such areas shall not exceed 10 feet (3048 mm). Multiple battery storage areas shall be separated from each other by not less than 20 feet (6096 mm) of open space.
322.4.3.4 Fire detection. Outdoor storage piles for lithium-ion or lithium metal batteries exceeding an aggregate area of 900 square feet (83.6 m²), regardless of whether such areas are open, under weather protection or in a prefabricated portable structure, shall be provided with an approved automatic fire detection and alarm system complying with Section 907. The fire detection system shall use radiant energy-sensing fire detection or thermal imaging detection.
322.4.3.5 Containers. Containers for outdoor storage of used or waste batteries shall be open-top and constructed of noncombustible materials; containers complying with DOTn regulations for lithium-ion and lithium metal transportation or shall be approved for battery collection and storage.
322.4.3.6 Weather protection. Where weather protection is provided for sheltering outdoor lithium-ion or lithium metal battery storage or use areas, such areas shall be considered outdoor storage or use where the weather protection structure complies with all of the following:
322.5 Other battery types general. Batteries in storage, other than lithium-ion or lithium metal batteries, with a volume more than 15 cubic feet (0.42 m³) within a fire area shall be in compliance with 322.5.1 through 322.5.6.
322.5.1 Structural and seismic design. Storage shall be protected against accidental dislodgement. Racks and shelving used for storage shall be designed in accordance with the International Building Code as applicable.
322.5.2 Impact protection. Where battery storage is subject to vehicle traffic, the storage shall be protected against impact in accordance with Section 312 or other approved method.
322.5.3 Battery charging. Battery charging shall be performed in accordance with manufacturer instructions utilizing listed or approved charging devices.
322.5.4 Mechanical exhaust system. Where battery charging can produce flammable gases a mechanical exhaust system shall be provided in accordance with the International Mechanical Code. The mechanical exhaust system shall be designed to limit the maximum concentration of flammable gas to 25 percent of the lower flammable limit (LFL) of the total volume of the room, or area during the worst-case event of simultaneous charging of batteries at the maximum charge rate, in accordance with nationally recognized standards.
322.5.5 Spill control. Spill control supplies shall be provided to control liquid electrolyte spills. The method shall be capable of controlling a spill from the single largest battery stored or handled.
322.5.6 Hazard warning signage. The entrances to battery storage areas shall be provided with warning signage that states, “BATTERY STORAGE AREA”, “ENERGIZED ELECTRICAL DEVICES” and lists the types of batteries present. The size, color and lettering shall be approved.
SECTION 323 IS ADDED TO READ AS FOLLOWS:
SECTION 323
BATTERY-POWERED DEVICES, TRUCKS, EQUIPMENT AND APPLIANCES
323.1 General. Battery-powered micromobility devices, battery-powered industrial trucks, battery-powered industrial equipment, battery-powered robotic equipment and battery-powered appliances shall be operated, charged and maintained in accordance with this section.
Exceptions:
323.1.1 Operational permit. An operational permit is required in accordance with Section 105.5 for battery storage, use and charging operations regulated by this section.
323.1.2 Battery charging operations. Battery charging operations shall be charged in accordance with their device listing and the manufacturer’s instructions using only the original equipment manufacturer-supplied charging equipment or charging equipment in accordance with the listing and manufacturer’s instructions.
323.1.2.1 Listing. Battery-powered equipment shall be listed and labeled in accordance with this section, where applicable and shall be operated and charged in accordance with its listing and the manufacturer’s instructions.
323.1.2.1.2 Battery-powered micromobility devices. Battery-powered micromobility devices shall be listed and labeled in accordance with UL 2272 or UL 2849, as applicable.
323.1.2.1.3 Battery-powered Automated mobile platforms (AMPs). Battery-powered Automated mobile platforms (AMPs) shall be listed and labeled in accordance with UL 3100.
323.1.2.1.4 Battery-powered robotic equipment. Battery-powered robotic equipment shall be listed and labeled in accordance with UL 3300.
323.1.2.1.5 Portable battery-powered equipment and appliances. Where installed or used, portable battery-powered equipment and appliances shall be listed and labeled in accordance with UL 2595 or the applicable standard for its use.
323.1.2.1.6 Hazardous (classified) locations. Battery powered micromobility devices, trucks, equipment, appliances and battery powered tools operated in in areas designated as hazardous (classified) locations in accordance with NFPA 70 shall be listed and labeled or approved for use in the environment intended.
323.1.3 Ventilation. Mechanical exhaust ventilation to the exterior shall be provided at the source in the charging location in accordance with Chapter 5 of the International Mechanical Code to prevent the dangerous accumulation of any flammable or other hazardous gases that are produced or discharged by the battery during normal charging operation.
323.1.4 Spill control and neutralization. Approved methods and materials shall be provided for the control and neutralization of spills of electrolyte or other hazardous materials in areas containing batteries as follows:
323.1.5 Battery charging locations. Charging of any battery powered industrial equipment, battery powered industrial truck, battery powered robotic equipment or battery-powered appliance in any occupancy shall be in an approved outdoor location or in an indoor area that complies with Section 323.2.
323.1.5.1 Prohibited locations. Repair or charging operations for business purposes shall not be permitted in the following locations:
323.2 Requirements for indoor charging locations. Indoor charging operations shall be provided with fire detection, fire suppression and other hazard mitigation measures as required by this Section.
323.2.1 Charging requirements for lead-acid batteries. Indoor charging areas for lead-acid batteries shall comply with Section 323.1 and 323.2.2.8.
323.2.2 Charging requirements for lithium-ion and lithium metal batteries. Indoor charging areas for lithium-ion and lithium metal batteries shall comply with Section 323.1 and 323.2.2.1 through 323.2.2.8.
323.2.2.1 Fire sprinklers. The fire area containing the indoor charging location shall be protected by an automatic sprinkler system installed in accordance with Section 903.3.1.1.
323.2.2.2 Fire detection. The indoor charging location shall be protected by a fire alarm system utilizing a smoke detection system, thermal imaging system or radiant energy-sensing fire detection system.
323.2.2.3 Electrical receptacles. The indoor charging location shall be provided with sufficient electrical receptacles to allow the charging equipment for each device to be directly connected to a receptacle installed in accordance with NFPA 70. The use of extension cords or relocatable power taps shall not be permitted.
323.2.2.4 Prohibited storage. Storage of combustible materials, combustible waste or hazardous materials shall not be permitted in the indoor charging location.
323.2.2.5 Means of egress. The charging operation shall not be conducted in or obstruct any required means of egress.
323.2.2.6 Storage enclosure. Removable batteries shall not be stacked or stored in an enclosed cabinet unless the cabinet is listed or is a specially designed battery containment enclosure approved for such purpose.
323.2.2.7 Battery charging separation. A minimum distance of 18 inches (457.2 mm) shall be maintained between each removable storage battery during charging operations unless each battery is isolated from neighboring batteries by an approved fire-resistant material or is within a specially designed rack or cabinet designed and approved for such purpose.
323.2.2.8 Device charging separation. A minimum of 18 inches (457.2 mm) shall be maintained between the locations of the batteries on each powered micromobility device, industrial truck, equipment, robot or appliance during charging operations.
323.3 Repairs. Repairs of battery-powered micromobility devices, battery-powered industrial trucks, battery-powered industrial equipment, battery-powered appliances and battery-powered robotic equipment shall be performed in approved locations outside of buildings or within buildings in areas specifically approved for that purpose.
323.4 Replacement batteries and chargers. Replacement batteries and chargers shall be equipment supplied by the manufacturer or the replacement battery or charger shall be in compliance with the manufacturer’s instructions for the equipment or device.
323.5 Fire safety plan. A fire safety plan shall be provided in accordance with Section 403.10.6. In addition, the fire safety plan shall include emergency response actions to be taken upon detection of a fire or possible fire involving lithium-ion or lithium metal battery storage.
323.6 Battery containment enclosures. Where provided to reduce separation distances required in Sections 323.2.2.7 or 323.2.2.8, containment enclosures for storage or charging of lithium-ion batteries or lithium-ion battery powered appliances shall comply with one of the following:
323.7 Battery exchange. Equipment or facilities providing battery exchange operations shall comply with Sections 323.7.1 and 323.7.2 and be approved by the fire code official.
323.7.1 Permit. Facilities providing battery exchange programs or equipment provided for exchange of lithium-ion batteries shall require an operational permit in accordance with Section 105.5.53.
323.7.2 Listed and labeled. Charging equipment utilized for battery exchange facilities or equipment shall be listed and labeled in accordance with UL 4900.
323.8 Damaged equipment. The charging of damaged devices or batteries shall be prohibited.
323.9 Battery-powered micromobility device batteries and chargers. The batteries and chargers used with battery-powered micromobility devices shall comply with this section.
323.9.1 Batteries and battery chargers. Batteries and battery chargers shall be in accordance with 3 23.9.1.1 through 323.9.1.4 as applicable.
323.9.1.1 Original equipment manufacturer’s devices. Batteries and battery chargers shall be provided as part of the listed battery powered micromobility device. This includes both non-removable and removable batteries.
323.9.1.2 Replacement batteries. Batteries not provided as part of the listed battery-powered micromobility device shall be compatible with the listed battery-powered micromobility device in accordance with the battery-powered micromobility device manufacturer’s instructions.
323.9.1.3 Replacement battery chargers. Single unit battery changers not provided as part of the listed battery-powered micromobility device shall be compatible with the listed battery-powered micromobility device in accordance with the battery-powered micromobility device manufacturer’s instructions.
323.9.1.4 Aftermarket devices. The use of batteries and battery chargers that do not comply with 323.9.1.2 and 323.9.1.3 shall be prohibited.
323.10 Micromobility charging equipment. Battery-powered micromobility device charging equipment that are multi-unit and do not comply with 323.9.1 shall be listed and labeled in accordance with UL 4900 and installed and operated in accordance with its listing and the manufacturer’s instructions. Micromobility charging equipment shall only be used to charge the battery-powered micromobility devices identified in the instructions. The installation location shall be approved by the fire code official.
SECTION 324 IS ADDED TO READ AS FOLLOWS:
SECTION 324
LITHIUM-ION AND LITHIUM METAL BATTERY RESEARCH, TESTING, MANUFACTURING OR RECYCLING
324.1 General. The research, testing, manufacturing, or recycling of lithium-ion and lithium metal batteries shall comply with this Section.
324.2 Scope. Any occupancy where one or more of the following operations involving lithium-ion or lithium metal battery components are conducted shall comply with Sections 324.3 through 324.11.
324.2.1 Collection and collating facilities. Facilities where batteries are only collected and collated for offsite recycling processing or disposal are not regulated by this section. Such facilities shall comply with Section 322.
324.3 Permits. An operational permit in accordance with Section 105.5.58 shall be required.
324.4 Fire Safety Plan. A fire safety plan shall be provided in accordance with Section 403.10.6.
324.5 Technical opinion and report. A technical opinion and report complying with Section 104.8.2 shall be prepared to evaluate the fire and explosion risks associated with research, testing, manufacturing, and recycling and to make recommendations including the necessary mitigation measures for all identified risks and for the fire and explosion protection design basis. The report shall be submitted to the fire code official for approval. The technical opinion and report shall specifically evaluate the following:
324.6 Storage. Lithium metal and lithium-ion batteries shall be stored in accordance with Section 322.
324.7 Equipment. Equipment used in research, testing, recycling, and manufacturing of lithium-ion and lithium metal batteries shall be designed for the intended use and evaluated in the technical report.
324.8 Fire protection. An approved automatic sprinkler system complying with Section 903.3 shall be provided in buildings where lithium ion or lithium metal batteries are researched, tested, manufactured, or recycled.
324.9 Fire detection. An approved automatic fire detection and alarm system complying with Section 907 shall be provided in buildings where lithium ion or lithium metal batteries are researched, tested, manufactured, or recycled.
324.10 Fire resistant separation. Indoor rooms or areas where any of the following operations are conducted shall be separated from other portions of the building by 2-hour fire-resistance-rated fire barriers and horizontal assemblies. Fire barriers shall be constructed in accordance with Section 707 of the International Building Code, and horizontal assemblies shall be constructed in accordance with Section 711 of the International Building Code.
324.11 Hazardous materials. Hazardous materials stored, used, handled, and generated in lithium ion and lithium metal battery manufacturing, research, testing, or recycling shall be in accordance with Chapters 50 through 67.
SECTION 326 IS ADDED TO READ AS FOLLOWS:
SECTION 325
MOBILE FOOD VENDOR VEHICLE PARKS
325.1 Mobile food vendor vehicle parks. A mobile food vendor vehicle park is an outdoor assembly occupancy and is required to have an operational permit set forth in Section 105.5.
325.1.1 Buildings. Construction permits and operational permits required for buildings and structures within, or associated with, a mobile food vendor vehicle park shall be obtained separately from the permits for the mobile food vendor vehicle park or mobile food vendor vehicles.
325.2 No Smoking. Smoking is prohibited within 10 ft of any mobile food vendor vehicles or Membrane structures within the mobile food vendor vehicle park. “NO SMOKING” signs shall be posted in conspicuous places throughout the mobile food vendor vehicle park.
325.3 Egress. Mobile food vendor vehicle parks shall be arranged to provide clear egress pathways with a minimum width of 44 inches.
325.4 Occupant load. Occupant load signs shall be posted for all mobile food vendor vehicle park areas where the perimeter or boundary is enclosed more than 50 percent, regardless of whether there is a roof. The occupant load shall be calculated at 15 square feet per occupant.
325.5 Buildings. All structures must be stable and free from damage that could pose a hazard to people or property.
325.6 Membrane structures. All tents and membrane structures shall comply with Chapter 31.
325.6.1 Flame resistant material. All umbrellas or other fabric used for weather protection shall be of materials meeting the flame propagation performance of Test Method 2 of NFPA 701.
325.7 Attachments. No flags, banners, electrical wires or other items shall be connected from one mobile food vendor vehicles to another, or from a mobile food vendor vehicle to a permanent structure.
325.8 Electrical. Electrical wiring and equipment at mobile food vendor vehicle parks shall comply with Section 603.
325.8.1 Outdoor electrical. All electrical wiring and equipment used outdoors must be protected against the weather and outside elements.
325.9 Fire department access. All mobile food vendor vehicle parks shall be provided with Fire Department vehicle access in accordance with Section 503.
zWhere any quantity of batteries or cells undergo destructive testing such as thermal, short circuit, impact, nail penetration, crushing, overcharge, or similar testing that can reasonably be expected to result in failure of the battery or cell.
325.9.1 Obstructing fire department access. Mobile food vendor vehicles are strictly prohibited from setting up in or blocking any fire apparatus access roads.
325.10 Emergency plans. Mobile food vendor vehicle parks must maintain a Fire Safety and Evacuation Plan as set forth in Chapter 4.
325.10.1 Emergency plans binder. Mobile food vendor vehicle parks shall have a copy of the fire safety and evacuation plans for the fire code official to review as set forth in Chapter 4.
325.10.2 Muster point. Mobile food vendor vehicle parks shall have a muster point with a sign labeling the location.
325.11 Compliance with Other Harris County Regulations. Before any fire code permits are issued, the applicant must first obtain all required permits in accordance with Harris County regulations.
SECTION 403.1 IS AMENDED TO READ AS FOLLOWS:
403.1 General. In addition to the requirements of Section 401, occupancies, uses and outdoor locations shall comply with the emergency preparedness requirements set forth in Sections 403.2 through 403.11.3.3. Where a fire safety and evacuation plan are required by Sections 403.2 through 403.10.6, evacuation drills shall be in accordance with Section 405 and employee training shall be in accordance with Section 406.
SECTIONS 403.7.1 AND 403.7.2 ARE AMENDED TO READ AS FOLLOWS:
403.7.1 Group I-1 occupancies. Group I-1 occupancies shall comply with Sections 403.7.1.1 through 403.7.1.7.
403.7.1.1 Fire safety and evacuation plan. The fire safety and evacuation plan required by Section 404 shall include a description of special staff actions. Plans shall include all of the following in addition to the requirements of Section 404:
403.7.2 Group I-2 occupancies. Group I-2 occupancies shall comply with Sections 403.7.2.1 through 403.7.2.4.
403.7.2.1 Fire safety and evacuation plan. The fire safety and evacuation plans required by Section 404 shall include a description of special staff actions. Plans shall include all of the following in addition to the requirements of Section 404:
SECTION 403.10.6 IS ADDED TO READ AS FOLLOWS:
403.10.6 Lithium-ion and lithium metal batteries. An approved fire safety and evacuation plan in accordance with Section 404 shall be prepared and maintained for occupancies that involve activities for the research and development, testing, manufacturing, handling or storage of lithium-ion batteries or lithium metal batteries, or the repair or servicing of vehicles powered by lithium-ion batteries or lithium metal batteries.
Exceptions: A fire safety and evacuation plan are not required for the storage or merchandizing of any of the following:
403.10.6.1 Mitigation planning. The approved fire safety and evacuation plan shall include thermal runaway event mitigation measures. These measures shall include activities undertaken to prevent thermal runaway, early detection of a thermal runaway event, reporting of unplanned thermal runaway events to the fire official and mitigation measures to be undertaken to limit the size and impact of the event on occupants and the facility.
SECTION 403.11.3.1 IS AMENDED TO READ AS FOLLOWS:
403.11.3.1 Number of crowd managers. Not fewer than two trained crowd managers, and not fewer than one trained crowd manager for each 250 persons or portion thereof, shall be provided for the gathering.
Exceptions:
SECTION 404.3 IS AMENDED AS FOLLOWS:
404.3 Maintenance. Fire safety, evacuation and lockdown plans shall be reviewed or updated annually or as necessitated by changes in staff assignments, occupancy, commodity storage or the physical arrangement of the building. Revised plans shall be submitted to the fire code official for review.
TABLE 405.3 IS AMENDED TO READ AS FOLLOWS:
TABLE 405.3
FIRE AND EVACUATION DRILL FREQUENCY AND PARTICIPATION
GROUP OR OCCUPANCY | FREQUENCY | PARTICIPATION |
Group A | Quarterly | Staff |
Group B b | Annually | All occupants |
Group B c (Ambulatory care facilities) | Quarterly on each shift a | Staff |
Group Bb (clinic, outpatient) | Annually | Staff |
Group E | Four per school year, two per semester | All occupants |
Group F | Annually | Employees |
Group I-1 | Semiannually on each shift a | All occupants |
Group I-2 | Quarterly on each shift a | Staff |
Group I-3 | Quarterly on each shift a | Staff |
Group I-4 | Monthly on each shift a | All occupants |
Group R-1 | Quarterly on each shift | Employees |
Group R-2 d | Four annually | All occupants |
Group R-4 | Semiannually on shift a | All occupants |
SECTIONS 503.1.1, 503.2.1 AND 503.3 ARE AMENDED TO READ AS FOLLOWS:
503.1.1 Buildings and facilities. Approved fire apparatus access roads shall be provided for every facility, building or portion of a building hereafter constructed or moved into or within the jurisdiction. The fire apparatus access road shall comply with the requirements of this section and Appendix D, and shall extend to within 150 feet (45 720 mm) of all portions of the facility and all portions of the exterior walls of the first story of the building as measured by an approved route around the exterior of the building or facility.
Exceptions:
503.2.1 Dimensions. Fire apparatus access roads shall have an unobstructed width of not less than 20 feet (6096 mm), exclusive of shoulders, except for approved security gates in accordance with Section 503.6, and an unobstructed vertical clearance of not less than 13 feet 6 inches (4115 mm). See Appendix D for additional requirements.
503.3 Marking. Fire apparatus access roads shall be marked by painted lines with a minimum width of 6 inches to show the boundaries of the lane. The paint shall be red traffic paint. The words “NO PARKING FIRE LANE” or “FIRE LANE NO PARKING” shall appear in 4inch high white letters at intervals no greater than 25 feet on the red border markings along both sides of the fire lanes. Where a curb is available, the striping shall be on both the vertical and horizontal faces of the curb. Where signs are installed to identify fire lanes, signs shall comply with Section D103.6 in Appendix D.
SECTION 503.6.1 IS ADDED TO READ AS FOLLOWS:
503.6.1 Required hardware. Electrically operated vehicular gates shall comply with Section 3110 of the International Building Code and the following:
SECTION 505.1 IS AMENDED TO READ AS FOLLOWS:
505.1 Address identification. New and existing buildings shall be provided with approved address identification. The address identification shall be legible and placed in a position that is visible from the street or road fronting the property. Address identification characters shall be reflective and contrast with their background. Address numbers shall be Arabic numbers or alphabetical letters. Numbers shall not be spelled out. Each character shall be not less than 4 inches (102 mm) high with a minimum stroke width of ½ inch (12.7 mm). Where required by the fire code official, address identification shall be provided in additional approved locations to facilitate emergency response. Where access is by means of a private road and the building cannot be viewed from the public way, a monument, pole or other sign or means shall be used to identify the structure. Address identification shall be maintained.
SECTION 505.1.1 IS ADDED TO READ AS FOLLOWS:
505.1.1 Additional identification required. In multi-tenant buildings where exterior exit doors face directions other than front of building, each door shall be labeled with business name and suite number or address. Numbers and letters shall contrast with their background and be Arabic numbers or alphabetical block letters not less than 2½ inches in height with a minimum stroke width of ¼ inch.
SECTIONS 506.1 AND 506.1.1 ARE AMENDED TO READ AS FOLLOWS:
506.1 Where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or firefighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type listed in accordance with UL 1037 and shall contain keys to gain necessary access as required by the fire code official. Key boxes, key box systems, keys and padlocks shall be manufactured and supplied by the Knox® Company, with a key cut for unincorporated Harris County. and a list identifying a minimum of three representatives who would be available to come to the location in the event of an afterhours emergency. The representatives list shall have decision making authority for the business. The list shall be legible and provide mobile phone numbers for each representative. The list shall be maintained and kept current.
506.1.1 Locks. An approved lock shall be installed on gates, doors or similar barriers where required by the fire code official. Only key locks, key boxes and key box systems that utilize a Knox® Company key, with a key cut for unincorporated Harris County shall be utilized.
SECTION 506.1.2 ITEM 6 IS AMENDED TO READ AS FOLLOWS:
6. The key box shall be mounted within 20 feet of the main elevator bank at the lobby nearest to the lowest level of fire department access.
SECTION 506.1.3 IS ADDED TO READ AS FOLLOWS:
506.1.3 Gated communities and multi-unit housing. To assure reasonable access for fire-fighting vehicles and equipment, emergency medical services vehicles and law enforcement officers, the owner or the owners association of a gated community or multi-unit housing project shall comply with this section.
506.1.3.1 Vehicular gates. Each vehicular gate to a gated community or multi-unit housing project shall be provided with a key box within sight of the gate and in close proximity outside the gate,
or the gate shall be secured with a chain and approved lock. The key box at all times must contain a key, card or code to open the gate, or a key switch or cable mechanism that overrides the key, card or code that normally opens the gate and allows the gate to be opened manually.
506.1.3.2 Pedestrian gates. Where pedestrian gates are installed, at least one pedestrian gate must have a key box within sight of the gate and in close proximity outside the gate. The key box at all times must contain a key, card, code, key switch or cable mechanism to open the gate. If there are multiple pedestrian gates present that utilize different keys, cards, or codes, the key box must contain:
506.1.3.3 Electrical power gate. Where access gates are powered by electricity, the gate must be designed to open without the use of a key, card, code or key switch if the gate loses electrical power.
SECTION 506 – SECTIONS 506.3 AND 506.4 ARE ADDED TO READ AS FOLLOWS:
506.3 Approved markings. The door of Key boxes shall be painted bright red so as to be readily noticeable with wording “FIRE DEPT” in white permanent letters not less than 1 inch in height.
506.4 Key box access. Approved access shall be provided and maintained for all key boxes. Storage, trash and other materials or objects shall not be placed or kept in such a manner that would prevent such equipment from being readily accessible.
SECTION 509.2.1 IS ADDED TO READ AS FOLLOWS:
509.2.1 Locking and securing. All rooms, suites, buildings, or occupancies which contain fire protection equipment shall be provided with a lock box for fire department access. Only key boxes and key box systems manufactured and supplied by the Knox® Company, with a key cut for unincorporated Harris County shall be utilized.
SECTION 510 IS AMENDED TO READ AS FOLLOWS:
510.1 Emergency responder communication coverage in new buildings. Approved in-building, two-way emergency responder communication coverage for emergency responders shall be provided in all new buildings. In-building, two-way emergency responder communication coverage within the building shall be based on the existing coverage levels of the public safety communication systems utilized by the jurisdiction, measured at the exterior of the building. This section shall not require improvement of the existing public safety communication systems. Frequencies will be determined by contacting Harris County Universal Services radio shop and the responding jurisdiction for the facility being tested. Coverage shall include the Harris County Radio System (TxWARN). The frequency range to be supported is 700-800 MHz (FDMA and TDMA). Additional VHF/UHF (150-174 MHz/408-512 MHz) frequency range may be required based upon the need of local public safety services or as otherwise required in writing by Harris County for public safety purposes.
Exceptions:
SECTION 510.3 IS AMENDED TO READ AS FOLLOWS:
510.3 Permit required. A permit for the installation of or modification to in-building, two-way emergency responder communication coverage systems and related equipment is required as specified in Section 105.6.4. Maintenance performed in accordance with this code is not considered a modification and does not require a permit. Application for permits must be submitted through Harris County engineering E-permits system and shall include:
SECTION 510.4.1.1 IS AMENDED TO READ AS FOLLOWS:
510.4.1.1 Minimum signal strength into the building.
The minimum downlink signal strength shall be sufficient to provide usable voice Communications throughout the coverage area as specified by the fire code official. The downlink signal level shall be sufficient to provide not less than a Delivered Audio Quality (DAQ) of 3.0 throughout the coverage area using either narrowband analog, digital or wideband LTE signals or an equivalent bit error rate
(BER), Signal-to-Interference- Plus-Noise Ratio (SINR) applicable to the technology for either analog or digital signals.
SECTION 510.4.1.2 IS AMENDED TO READ AS FOLLOWS:
510.4.1.2 Minimum signal strength out of the building.
The minimum uplink signal strength shall be sufficient to provide usable voice communications throughout the coverage area as specified by the fire code official. The uplink signal level shall be sufficient to provide not less than a delivered audio quality DAQ of 3.0 using either narrowband analog, digital or wideband LTE digital signals or an equivalent bit error rate (BER),or an equivalent SINR applicable to the technology for either analog or digital signals.
SECTION 510.4.2.2 IS AMENDED TO READ AS FOLLOWS:
510.4.2.2 Technical criteria. The fire code official in correlation with Harris County Universal services shall maintain a document providing the specific technical information and requirements for the in-building, two-way emergency responder communication coverage system. This document shall contain, but not be limited to, the various frequencies required, the location of radio sites, the effective radiated power of radio sites, the maximum propagation delay in microseconds, the applications being used and other supporting technical information necessary for system design.
SECTION 510.4.2.7 IS AMENDED TO READ AS FOLLOWS:
510.4.2.7 Design documents. The fire code official shall have the authority to require “as-built” design documents and specifications for in-building, two-way emergency responder communication coverage systems. The documents shall be in. PDF format and included with the application for permit.
SECTION 510.6.1 IS AMENDED TO READ AS FOLLOWS:
510.6.1 Testing and proof of compliance. The owner of the building or owner’s authorized agent shall have the in-building, two-way emergency responder communication enhancement system inspected and tested annually or where structural changes occur, including additions or remodels that could materially change the original field performance tests. Testing shall consist of the following:
1. In-building coverage test as described in Section 510.5.4.
2. Signal boosters shall be tested to verify that the gain is the same as it was upon initial installation and acceptance or set to optimize the performance of the system.
3. Backup batteries and power supplies shall be tested under load of a period of 1 hour to verify that they will properly operate during an actual power outage. If within the 1-hour test period the battery exhibits symptoms of failure, the test shall be extended for additional 1-hour periods until the integrity of the battery can be determined.
4. All active components shall be checked to verify operation within the manufacturer’s specifications.
At the conclusion of the testing, a report, which shall verify compliance with Section 510.5.4, shall be submitted to the fire code official.
In addition to annual testing, all emergency responder communication enhancement systems shall undergo full system re-permitting every five (5) years. This re-permitting process shall include comprehensive testing (including grid report), documentation, and submission for review and approval by the fire code official, regardless of whether structural changes have occurred.
SECTION 611 IS ADDED TO READ AS FOLLOWS:
SECTION 611
ELECTRIC VEHICLE CHARGING STATIONS
611.1 General. Electrical vehicle charging stations shall comply with this section.
611.1.1 Location of charging stations. Battery electric vehicle charging stations as follows:
611.2 Emergency Disconnects/Shutoff Switches. Locations containing electric vehicle charging stations shall be provided with a clearly identified emergency disconnect/estops, provided with ready access and installed in an approved location. The emergency power disconnect/shutoff switch shall shut off all power from the charging station when activated.
611.2.1 Alternative disconnects. Where approved, a disconnect provided to comply with NFPA 70 can be utilized to meet the disconnect requirement when it is clearly identified, and the location is provided with ready access.
611.2.2 Location. Emergency disconnect/shutoff switches shall be installed not more than 100 feet and not less than 20 feet from the charging stations.
611.2.3 Height. Emergency disconnect/shutoff switches shall be not less than 42 inches (1067 mm) and not more than 48 inches (1372 mm) measured vertically above the walking surface.
611.2.4 Labeling. Emergency disconnect switches shall be clearly visible and labeled to correspond to the associated charging station. The emergency disconnect/shutoff shall be labeled “EMERGENCY ELECTRIC VEHICLE CHARGER DISCONNECT” in letters not less than 4 inches high.
611.2.5 Manual reset. Emergency disconnect/shutoff switches shall require manual intervention to reset after activation.
611.3 Fire extinguishers. Approved portable fire extinguishers complying with Section 906 with a minimum rating of 2-A:20-B:C shall be provided and located such that an extinguisher is not more than 75 feet (23 860 mm) from electric vehicle charging stations.
SECTION 705.2.6 IS AMENDED TO READ AS FOLLOWS:
705.2.6 Testing. Horizontal and vertical sliding and rolling fire doors shall be inspected and tested annually by a trained technician in accordance with NFPA 80 to confirm proper operation and full closure. Records of inspections and testing shall be maintained.
SECTION 901.4.7 IS AMENDED TO READ AS FOLLOWS:
901.4.7 Pump and riser room size. Fire pump rooms and automatic sprinkler system riser rooms shall be designed with adequate space for all equipment necessary for the installation, as defined by the manufacturer, with sufficient working space around the stationary equipment. Clearances around equipment to elements of permanent construction, including other installed equipment and appliances, shall be sufficient to allow inspection, service, repair or replacement without removing such elements of permanent construction or disabling the function of a required fire-resistance-rated assembly. Fire pump and automatic sprinkler system riser rooms shall be provided with doors and unobstructed passageways large enough to allow removal of the largest piece of equipment. Sufficient clearances around equipment and permanent construction shall be maintained and kept free of storage and other obstructions.
901.4.7.1 Access. Automatic sprinkler system risers, fire pumps and controllers shall be located in an automatic sprinkler riser room or a fire pump room readily accessible. Fire sprinkler riser rooms shall have an exterior access door with a key box in accordance with Section 506 509.2.1. The door shall be permitted to be locked provided that the key is available at all times.
Exceptions: Automatic fire sprinkler control valves that are located on the exterior of the building, or in a vault, or in a readily accessible area outside of the building.
901.4.7.2 Marking on access doors. Access doors for automatic sprinkler system riser rooms and fire pump rooms shall be labeled with an approved sign. The lettering shall be reflective and in contrasting color to the background. Letters shall have a minimum height of 2 inches (51 mm) with a minimum stroke of 3/8 inch (10 mm).
901.4.7.3 Environment. Automatic sprinkler system riser rooms and fire pump rooms shall be maintained at a temperature of not less than 40°F (4°C) and other environmental requirements as specified by the manufacturer of the installed equipment. Heating units shall be permanently installed.
901.4.7.4 Lighting. Permanently installed artificial illumination on both interior and exterior sides of the access door shall be provided in the automatic sprinkler system riser rooms and fire pump rooms.
901.4.7.5 Fire sprinkler riser room separation. Automatic fire sprinkler riser rooms shall be separated from the remainder of the building by 1-hour fire barriers or 1-hour horizontal assemblies.
TABLE 901.6.1 IS AMENDED TO READ AS FOLLOWS:
TABLE 901.6.1
FIRE PROTECTION SYSTEM MAINTENANCE STANDARDS
| SYSTEM | STANDARD |
| Portable fire extinguishers | NFPA 10 |
| Carbon dioxide fire-extinguishing system | NFPA 12 |
| Halon 1301 fire-extinguishing system | NFPA 12A |
| Dry-chemical extinguishing systems | NFPA 17 |
| Wet-chemical extinguishing systems | NFPA 17A |
| Water-based fire protection systems | NFPA 25 |
| Fire alarm systems | NFPA 72 |
| Mechanical smoke exhaust systems | NFPA 204 |
| Smoke and heat vents | NFPA 204 |
| Water-mist systems | NFPA 750 |
| Clean agent extinguishing systems | NFPA 2001 |
| Aerosol fire extinguishing systems | NFPA 2010 |
SECTION 903.2.2 IS AMENDED TO READ AS FOLLOWS:
903.2.2 Group B. An automatic sprinkler system shall be provided for Group B occupancies as required in Sections 903.2.2.1 and 903.2.2.2.
903.2.2.1 Ambulatory care facilities. An automatic sprinkler system shall be installed throughout the entire floor containing an ambulatory care facility where either of the following conditions exist at any time:
In buildings where ambulatory care is provided on levels other than the level of exit discharge, an automatic sprinkler system shall be installed throughout the entire floor as well as all floors below where such care is provided, and all floors between the level of ambulatory care and the nearest level of exit discharge, the level of exit discharge, and all floors below the level of exit discharge.
Exception: Floors classified as an open parking garage are not required to be sprinklered.
903.2.2.2 Lithium-ion or lithium metal battery research and development. An automatic sprinkler system shall be installed throughout fire areas utilized for the research and development or testing of lithium-ion or lithium metal batteries.
SECTION 903.2.4 IS AMENDED TO READ AS FOLLOWS:
903.2.4 Group F-1. An automatic sprinkler system shall be provided throughout all buildings containing a Group F-1 occupancy where one of the following conditions exists:
SECTION 903.2.4.4 IS ADDED TO READ AS FOLLOWS:
903.2.4.4 Combustible waste sorting and transfer. An automatic sprinkler system shall be provided throughout F-1 occupancy fire areas that contain combustible waste sorting and transfer operations in excess of 5,000 square feet (464.5 m²) in area.
SECTION 903.2.7.3 IS ADDED TO READ AS FOLLOWS:
903.2.7.3 Lithium-ion or lithium metal battery storage. An automatic sprinkler system shall be provided in a room or space within a Group M occupancy where required for the storage of lithium-ion or lithium metal batteries by Section 322 or Chapter 32.
SECTIONS 903.2.9 AND 903.2.9.1 ARE AMENDED BY ADDING ITEM 5 TO READ AS FOLLOWS:
903.2.9 Group S-1.
902.2.9.1 Repair garages.
SECTIONS 903.2.9.4 IS AMENDED TO READ AS FOLLOWS:
903.2.9.4 Group S-1 upholstered furniture and mattresses. An automatic sprinkler system shall be provided throughout a Group S-1 fire area where the area used for the storage of upholstered furniture or mattresses exceeds 2,500 square feet (232 m²).
Exception: Self-service storage facilities complying with Section 903.2.9.5.
SECTIONS 903.2.9.5 IS ADDED TO READ AS FOLLOWS:
903.2.9.5 Self-service storage facilities. An automatic sprinkler system shall be provided throughout buildings used for self-service storage facilities.
Exception: Self-service storage facilities with fire areas not greater than 12,000 square feet and not greater than one story above grade plane where all storage spaces can be accessed directly from the exterior.
SECTIONS 903.2.10.3 IS ADDED TO READ AS FOLLOWS:
903.2.10.3 Lithium-ion or lithium metal powered vehicles. An approved automatic sprinkler system shall be provided throughout fire areas used for the parking or storage of lithium-ion or lithium metal powered vehicles where the fire area exceeds 500 square feet (46.4 m²).
TABLE 903.2.11.6 IS AMENDED BY ADDING A NEW ROW TO READ AS FOLLOWS:
TABLE 903.2.11.6
ADDITIONAL REQURIED FIRE PROTECTION SYSTEMS
|
SECTION |
SUBJECT |
|
324.2.1 |
Lithium-ion and lithium metal battery charging locations |
SECTIONS 903.3.1.1.1 IS AMENDED TO READ AS FOLLOWS:
903.3.1.1.1 Exempt locations. Where approved by the fire code official, automatic sprinklers may be omitted in the following rooms or areas where such rooms or areas are protected with an approved automatic fire detection system in accordance with Section 907.2 that will respond to visible or invisible particles of combustion. Sprinklers shall not be omitted from a room merely because it is damp, fire-resistance-rated construction or contains electrical equipment.
SECTIONS 903.3.1.1.3, 903.3.1.1.4 AND 903.3.1.1.5 ARE ADDED TO READ AS FOLLOWS:
903.3.1.1.3 Main protection. Fire sprinkler mains and cross mains installed in un-sprinklered areas shall be protected from mechanical and fire damage with fire sprinklers or by enclosing in a 1-hour rated chase.
903.3.1.1.4 Lithium-Ion or lithium metal batteries. Where automatic sprinkler systems are required by the sections listed in Table 903.3.1.1.4, for areas containing lithium-ion or lithium metal batteries, the design of the system shall be based on a series of fire tests. Such tests shall be conducted or witnessed and reported by an approved testing laboratory involving test scenarios. A report prepared by a registered design professional with expertise in fire protection engineering shall be provided to the fire code official for review and approval in accordance with Section 104.8.2 and shall that address the range of variables associated with the intended arrangement of the hazards to be protected.
TABLE 903.3.1.1.4
AUTOMATIC SPRINKLER SYSTEMS FOR LITHIUM-ION AND LITHIUM METAL BATTERY AREAS
|
SECTION/TABLE |
AREA REQUIRED |
|
Table 3206.2 |
High-hazard commodity |
|
Section 322 |
Battery storage |
|
Section 903.2.2 |
Research and development laboratory |
|
Section 903.2.4 |
Manufacturing |
|
Section 903.2.7.3 |
Group M occupancy |
|
Section 1207.6 |
Energy storage systems |
903.3.1.1.5 Required minimum safety pressure. A safety factor of 5 psi minimum shall be provided for hydraulically calculated fire sprinkler pressure demands.
SECTION 903.3.1.2.4 IS ADDED TO READ AS FOLLOWS:
903.3.1.2.4 Required minimum safety pressure. A safety factor of 5 psi minimum shall be provided for hydraulically calculated fire sprinkler pressure demands.
SECTIONS 903.4.1 AND 903.4.2 ARE AMENDED TO READ AS FOLLOWS:
903.4.1 Monitoring. Alarms, supervisory and trouble signals shall be transmitted to an approved supervising station, through a dedicated function fire alarm control unit or a fire alarm control panel. Each alarm, supervisory and trouble signal shall be addressable and identify the building, zone or riser location when initiated or activated. When approved by the Fire Code Official, a performance-based alternative may be approved.
Exceptions:
In occupancies required to be equipped with a fire alarm system, the backflow preventer valves shall be electrically supervised by a tamper switch installed in accordance with NFPA 72 and separately annunciated.
903.4.2 Alarms. An approved audible device, located on the exterior of the building in an approved location, shall be connected to each automatic sprinkler system. Such sprinkler waterflow alarm devices shall be activated by water flow equivalent to the flow of a single sprinkler of the smallest orifice size installed in the system. Where a fire alarm system is installed, actuation of the automatic sprinkler system shall actuate the building fire alarm system. Where a fire alarm system is not installed, occupant notification in accordance with Section 903.4.2.1 shall be provided and activated upon water flow.
903.4.2.1. Occupancy notification. Occupant notification shall be provided in accordance with Section 907.5 in all areas protected by the automatic sprinkler system.
Exception: Group S Warehouse areas with no public access.
SECTION 904.13.1 IS AMENDED TO READ AS FOLLOWS:
904.13.1 Manual system operation. A manual actuation device shall be located at or near a means of egress from the cooking area not less than 10 feet (3048 mm) and not more than 20 feet (6096 mm) from the kitchen exhaust system. The manual actuation device shall be installed not more than 48 inches (1200 mm) nor less than 42 inches (1067 mm) above the floor and shall clearly identify the hazard protected. The manual actuation shall require a maximum force of 40 pounds (178 N) and a maximum movement of 14 inches (356 mm) to actuate the fire suppression system. An unobstructed path of not less than 36 inches (915 mm) wide to the manual actuation device shall be maintained.
Exception: Automatic sprinkler systems shall not be required to be equipped with manual actuation means.
SECTION 904.14.1.1 IS AMENDED TO READ AS FOLLOWS:
904.14.1.1 Automatic fire-extinguishing system. The domestic recirculating or exterior vented cooking hood provided over the cooktop or range shall be equipped with an approved automatic fire-extinguishing system complying with the following:
Where a facility is not equipped with a fire alarm system, the fire-extinguishing system shall have audible and visual notification provided in a conspicuous area within the facility to notify occupants of the activation of the fire-extinguishing system.
SECTIONS 907.2, 907.2.1 ARE AMENDED TO READ AS FOLLOWS:
907.2 Where required—new buildings and structures. An approved fire alarm system installed in accordance with the provisions of this code and NFPA 72 shall be provided in new buildings and structures in accordance with Sections 907.2.1 through 907.2.24 and provide occupant notification in accordance with Section 907.5, unless other requirements are provided by another section of this code. Fire alarm will include a minimum of 50 addressable points.
Only one fire alarm system shall be installed per building. Multiple points of silence and reset are prohibited on a single fire alarm system, except for the fire alarm control unit and the annunciator panel required in Section 907.5.1.
Exceptions:
Not fewer than one manual fire alarm box shall be provided in an approved location to initiate a fire alarm signal for fire alarm systems employing automatic fire detectors or waterflow detection devices. Where other sections of this code allow elimination of fire alarm boxes due to sprinklers, a single fire alarm box shall be installed.
Exceptions:
907.2.1 Group A. A manual fire alarm system that activates the occupant notification system in accordance with Section 907.5 shall be installed in Group A occupancies where the occupant load due to the assembly occupancy is 100. Where multiple Group A occupancies are located within a building, the aggregate occupant load of the Group A occupancies shall be considered unless they are separated from one another in accordance with Section 707.3.10 of the International Building Code. Portions of Group E occupancies occupied for assembly purposes shall be provided with a fire alarm system as required for the Group E occupancy.
Exception: Manual fire alarm boxes are not required where the building is equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.1 and the occupant notification appliances will activate throughout the notification zones upon sprinkler water flow.
SECTION 907.2.1.3 IS ADDED TO READ AS FOLLOWS:
907.2.1.3 – Group A-2. A manual fire alarm system that activates the occupant notification system in accordance with Section 907.5 shall be installed in Group A-2 occupancies where alcohol is consumed.
SECTIONS 907.2.3.1 AND 907.2.3.2 IS ADDED TO READ AS FOLLOWS:
907.2.3.1 Pre-K areas in Group E occupancies. Smoke detection shall be provided throughout areas or rooms that can be occupied by Pre-K children.
907.2.3.2 Temporary Education Occupancies. All temporary educational occupancies not equipped with a sprinkler system shall provide smoke detection throughout the occupiable space. Any initiation and notification devices installed in these occupancies shall be connected to the campus fire alarm system.
THE FIRST PARAGRAPH OF SECTION 907.2.6 IS AMENDED TO READ AS FOLLOWS:
907.2.6 Group I. A manual fire alarm system that activates the occupant notification system in accordance with Section 907.5 shall be installed in Group I occupancies. An automatic smoke detection system that activates the occupant notification system in accordance with Section 907.5 shall be provided in accordance with Sections 907.2.6.1 through 907.2.6.4 and 907.4.3.1.
SECTION 907.2.6.4 IS ADDED TO READ AS FOLLOWS:
907.2.6.4 Group I-4 occupancies. A manual fire alarm system that initiates the occupant notification signal utilizing an emergency voice/alarm communication system meeting the requirements of Section 907.5.2.2 and installed in accordance with Section 907.6 shall be installed in Group I-4 licensed daycare centers. Where automatic sprinkler systems are installed, such systems shall be connected to the building fire alarm system. Smoke detection shall be provided in areas or rooms that can be occupied by children, and where required in Section 907.4.3.1.
Exceptions: In Group I-4 occupancies an emergency voice/alarm communication system is not required when the facility occupancy load is 100 or less.
SECTION 907.2.23 IS AMENDED TO READ AS FOLLOWS:
907.2.23 Energy storage systems. An automatic smoke detection system, thermal imaging detection system or radiant-energy detection system shall be installed in rooms, areas and walk-in units containing energy storage systems as required in Section 1207.
SECTIONS 907.2.24 IS ADDED TO READ AS FOLLOWS:
907.2.24 Combustible waste sorting and transfer. A radiant-energy fire detection system or a thermal imaging fire detection system shall be provided throughout Group F-1 fire areas that contain combustible waste sorting and transfer operations in excess of 5,000 square feet (464.5 m²) in area.
SECTION 907.4.1 IS AMENDED TO READ AS FOLLOWS:
907.4.1 Protection of fire alarm control unit. A single smoke detector shall be provided at the location of each fire alarm control unit, notification appliance circuit power extenders and supervising station transmitting equipment.
Exception: Where ambient conditions prohibit installation of a smoke detector, a heat detector shall be permitted.
SECTION 907.4.3.1 IS ADDED TO READ AS FOLLOWS:
907.4.3.1 Required smoke detection. All required fire alarm systems shall also include smoke detectors in each mechanical equipment, electrical, transformer, telephone equipment, corridors, lobbies, storage rooms larger than 200 square feet, elevator machine rooms, elevator lobbies and other areas determined to be a special hazard by the Fire Code Official.
SECTION 907.5.1 IS AMENDED TO READ AS FOLLOWS:
907.5.1 Alarm activation and annunciation. Upon activation, fire alarm systems shall initiate occupant notification and shall annunciate at the fire alarm control unit, or where allowed elsewhere by Section 907, at a constantly attended location. Annunciation shall also be provided at the main entrance to the building.
SECTIONS 907.5.2.2 AND 907.5.2.2.2 ARE AMENDED TO READ AS FOLLOWS:
907.5.2.2 Emergency voice/alarm communication systems. Emergency voice/alarm communication systems required by this code shall be designed and installed in accordance with NFPA 72. The operation of any automatic fire detector, sprinkler waterflow device or manual fire alarm box shall automatically sound an alert tone followed by voice instructions giving approved information and directions for a general or staged evacuation in accordance with the building’s fire safety and evacuation plans required by Section 404. The voice instructions shall continue until the fire alarm system is silenced or reset, annunciating between alert tones. In high-rise buildings, the system shall operate on at least the alarming floor, the floor above and the floor below. Speakers shall be provided throughout the building by paging zones. At a minimum, paging zones shall be provided as follows:
Exception: In Group I-1 and I-2 occupancies, the alarm shall sound in a constantly attended area and a general occupant notification shall be broadcast over the overhead page.
907.5.2.2.2 Live voice messages. The emergency voice/alarm communication system shall have the capability to broadcast live voice messages by paging zones on a selective and all-call basis. Emergency voice/alarm communication systems shall be programed to return to the pre-recorded messaging or alarm signaling immediately following live voice messaging for continued occupant notification.
SECTION 907.6.2.1 IS ADDED TO READ AS FOLLOWS:
907.6.2.1 Fire Alarm surge protectors. Each fire alarm related component necessary for the function of all associated notification and initiation devices, shall be equipped with surge protection, installed in accordance with manufacturer specifications. These components include but are not limited to, signaling line circuits (SLC), notification appliance circuits (NAC), telephone lines, and AC power connections.
SECTIONS 907.6.6 IS AMENDED TO READ AS FOLLOWS:
907.6.6 Monitoring. Alarms, supervisory and trouble signals shall be transmitted to an approved supervising station. Each alarm, supervisory and trouble signal shall identify the building, room and location of the specific device that was initiated or activated. When approved by the Fire Code Official, a performance-based alternative may be approved.
Exception: Monitoring by a supervising station is not required for:
1. Single- and multiple-station smoke alarms required by Section 907.2.11.
2. Smoke detectors in Group I-3 occupancies.
3. Automatic sprinkler systems in one- and two-family dwellings.
SECTIONS 907.8.4.1 IS ADDED TO READ AS FOLLOWS:
907.8.4.1 Fire alarm control unit replacement. Where maintenance of an existing fire alarm system involves replacement or upgrade of the fire alarm control unit and requires a new installation tag and certification, the entire fire alarm system shall be considered a new system and meet the requirements of Section 907.2.
Exception: Replacement of a fire alarm control unit with the exact same make and model as the existing panel shall not be considered a new system, provided no changes are made to system wiring, device layout, or programming that would otherwise require compliance with Section 907.2. Contractors will have to submit documentation outlining prior installation and replacement panel specifications. The permit will require an onsite inspection to verify functionality.
SECTION 912.6 IS AMENDED TO READ AS FOLLOWS:
912.6 Backflow protection. The potable water supply to automatic sprinkler and standpipe systems shall be protected against backflow as required by the Local Water Authority.
SECTIONS 913.2.1.1, 913.6, 913.7 AND 913.8 ARE ADDED TO READ AS FOLLOWS:
913.2.1.1 Fire pump rooms. Fire pump rooms shall have an exterior access door with a Key Box system compliant with 506.1 for fire department access. Illumination shall be provided on both the exterior and interior sides of the access door and the door shall be clearly marked and identified per Section 509.2.1. Storage rooms shall not be used for a fire pump room.
913.6 Water supply for fire pumps. Where a fire protection system is connected to a municipal type of water system or utility district water line, the water authority having jurisdiction shall determine the required backflow prevention necessary to protect their water lines. Equipment and devices installed to guard against possible contamination of the water system shall comply with the manufacturer’s specifications and national standards.
913.7 Electrical outage history report. Where an electric-driven fire pump is proposed, an electric service outage report shall be provided. The report shall come from the local utility provider and include a list of all electrical outages for a period of the past 24 months for the permitted address.
913.8 Standby power supply for fire pumps. Standby power supply is required for electric-driven fire pump installations in buildings classified as Critical Facilities, and when required by the Fire Code Official after consideration of the occupancy classification. Such standby power supplies shall meet the requirements of Section 1203.2.20.
SECTION 914.7.1 IS AMENDED TO READ AS FOLLOWS:
914.7.1 Automatic sprinkler system. Buildings containing special amusement areas shall be equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1. Where the special amusement area is temporary, the sprinkler water supply shall be of an approved temporary means.
Exceptions:
SECTION 1101.2.1 IS ADDED TO READ AS FOLLOWS:
1101.2.1 Applicability. All existing buildings, structures, facilities, or occupancies are subject to review and permitting under this chapter except under the following conditions:
Existing occupancies that do not meet the definition of substantial improvement and have been permitted after the adoption of the Harris County Fire Code, January 1, 2005, and issued a Certificate of Compliance that has not closed or vacated for more than 31 days shall be subject to review under
this chapter. Any building of new walls, enclosing openings, or changing the floor plan, constitutes construction and will require chapter 11 fire code review. The fire code official has the authority to require compliance with this chapter for any existing building or structure in the interest of fire and life safety.
SECTION 1103.5.1 IS AMENDED TO READ AS FOLLOWS:
1103.5.1 Group A-2. Where alcoholic beverages are consumed in a Group A-2 occupancy having an occupant load of 300 or more, the fire area containing the Group A-2 occupancy shall be equipped with an automatic sprinkler system in accordance with Section 903.3.1.1 and occupancy notification in accordance with Section 903.4.2.1.
SECTION 1103.7 IS AMENDED TO READ AS FOLLOWS:
1103.7 Fire alarm systems. An approved fire alarm system shall be installed in existing buildings and structures in accordance with Sections 1103.7.1 through 1103.7.7 and provide occupant notification in accordance with Section 907.5 unless other requirements are provided by other sections of this code.
Exception: Occupancies with an existing, previously approved fire alarm system.
1103.7.1 Group A-1 & A-2. A manual fire alarm system shall be installed in existing Group A-1 & A-2 Occupancies where the occupancy load is 300 or greater or where alcohol is being consumed in accordance with Section 907.2.1.
1103.7.2 Group E. A fire alarm system shall be installed in existing Group E occupancies in accordance with Section 907.2.3.
Exceptions:
1103.7.3 Group I-1. An automatic fire alarm system shall be installed in existing Group I-1 facilities in accordance with Section 907.2.6.1.
Exception: Where each sleeping room has a means of egress door opening directly to an exterior egress balcony that leads directly to the exits in accordance with Section 1021, and the building is not more than three stories in height.
1103.7.4 Group I-2. In Group I-2, an automatic fire alarm system shall be installed in accordance with Section 1105.10.
1103.7.5 Group I-3. An automatic and manual fire alarm system shall be installed in existing Group I-3 occupancies in accordance with Section 907.2.6.3.
1103.7.6 Group R-1. A fire alarm system and smoke alarms shall be installed in existing Group R-1 occupancies in accordance with Sections 1103.7.6.1 through 1103.7.6.2.1.
1103.7.6.1 Group R-1 hotel and motel manual fire alarm system. A manual fire alarm system that activates the occupant notification system in accordance with Section 907.5 shall be installed in existing Group R-1 hotels and motels more than one story in height or with more than 20 sleeping units.
Exceptions:
1103.7.6.1.1 Group R-1 hotel and motel automatic smoke detection system. An automatic smoke detection system that activates the occupant notification system in accordance with Section 907.5 shall be installed in existing Group R-1 hotels and motels throughout all interior corridors serving sleeping rooms not equipped with an approved, supervised sprinkler system installed in accordance with Section 903.
Exception: An automatic smoke detection system is not required in buildings that do not have interior corridors serving sleeping units and where each sleeping unit has a means of egress door opening directly to an exit or to an exterior exit access that leads directly to an exit.
1103.7.6.2 Group R-1 boarding and rooming houses manual fire alarm system. A manual fire alarm system that activates the occupant notification system in accordance with Section 907.5 shall be installed in existing Group R-1 boarding and rooming houses.
Exception: Buildings less than two stories in height where all sleeping units, attics and crawl spaces are separated by 1-hour fire-resistance-rated construction and each sleeping unit has direct access to a public way, egress court or yard.
1103.7.6.2.1 Group R-1 boarding and rooming houses automatic smoke detection system. An automatic smoke detection system that activates the occupant notification system in accordance with Section 907.5 shall be installed in existing Group R-1 boarding and rooming houses throughout all interior corridors serving sleeping units not equipped with an approved, supervised sprinkler system installed in accordance with Section 903.
Exception: Buildings equipped with single-station smoke alarms meeting or exceeding the requirements of Section 907.2.11.1 and where the fire alarm system includes not less than one manual fire alarm box per floor arranged to initiate the alarm.
1103.7.7 Group R-2. A manual fire alarm system that activates the occupant notification system in accordance with Section 907.5 shall be installed in existing Group R-2 occupancies more than three stories in height or with more than 16 dwelling or sleeping units.
Exceptions:
4.1 Each dwelling unit is separated from other contiguous dwelling units by fire barriers having a fire-resistance rating of not less than ¾ hour.
4.2 Each dwelling unit is provided with hard wired, interconnected smoke alarms as required for new construction in Section 907.2.11.
5.Existing fire alarm systems that are compliant with the State of Texas rules and regulations and are not part of a substantial improvement repair or replacement.
SECTION 1103.11 IS ADDED TO READ AS FOLLOWS:
1103.11 Secondary power for Group I-1 and I-2. Existing Group I-1 assisted living facilities and Group I-2 nursing homes shall be provided with the ability to provide secondary power as required in Section 1203.2.21. The facility shall comply with Section 1203.2.21 prior to any of the following:
SECTION 1103.12 IS ADDED TO READ AS FOLLOWS:
1103.12 Fire Apparatus Access Roads for Existing Buildings. The fire code official is authorized to require fire apparatus access roads to be provided for existing buildings when it is determined that the existing access roads do not provide sufficient access to buildings to enable efficient fire suppression and rescue operations
SECTION 1103.13.1 IS ADDED TO READ AS FOLLOWS:
1103.13.1 AUTOMATED EXTERNAL DEFIBRILLATOR (AED) INSPECTIONS IN SCHOOLS. Fire safety inspections of public, private, and open-enrollment charter schools shall include verification of the operational status of all automated external defibrillators (AEDs) located on the premises. Verification shall be conducted by the fire code official or an authorized representative in accordance with applicable state law.
1103.13.2 Inspection Criteria
AEDs shall be subject to visual inspection and review of maintenance documentation. Verification shall include confirmation that:
The device appears ready for use.
The status indicator, if present, indicates a “ready” condition.
Electrodes and battery are within the manufacturer’s expiration date.
The device is free of physical damage that may impair function.
Audible alert functions, if equipped, are operational.
The device is presented upon request.
Maintenance or inspection documentation required by law is available for review.
1103.13.3 Report. The fire code official shall issue a written report of findings to the school authority having jurisdiction. The report shall identify the date, time, and method of delivery.
1103.13.4 Record retention. A copy of the inspection report shall be maintained on site at the campus for which it was issued. Reports shall be retained in accordance with local and state record retention requirements.
1103.13.5 Referenced standards. Verification shall be conducted in accordance with:
SECTION 1201.1 IS AMENDED TO READ AS FOLLOWS:
1201.1 Scope. The provisions of this chapter shall apply to the installation, operation, maintenance, repair, retrofitting, testing, commissioning, and decommissioning of energy systems used for generating or storing energy, including but not limited to energy storage systems under the exclusive control of an electric utility or lawfully designated agency. It shall not apply to equipment associated with the generation, control, transformation, transmission, or distribution of energy installations that is under the exclusive control of an electric utility or lawfully designated agency. Energy storage systems regulated by Section 1207 shall comply with this chapter, as appropriate, and NFPA 855.
SECTION 1203.1.8 IS AMENDED TO READ AS FOLLOWS:
1203.1.8 Group I-2 occupancies. In Group I-2 occupancies located in flood hazard areas per the Regulations of Harris County, Texas for Floodplain Management, where new essential electrical systems are installed, and where new or replacement essential electrical system generators are installed, the system and generator shall be located and installed in accordance with the Regulations of Harris County, Texas for Floodplain Management.
SECTION 1203.2 IS AMENDED TO READ AS FOLLOWS:
1203.2 Where required. Emergency and standby power systems shall be provided where required by Sections 1203.2.1 through 1203.2.20.
SECTION 1203.2.20 IS ADDED TO READ AS FOLLOWS:
1203.2.20 Critical facilities. Critical facilities shall be provided with standby or emergency power as required in Sections 1203.2.20.1 and 1203.2.20.2.
1203.2.20.1 Standby power. Standby power shall be provided for the following loads:
1203.2.20.2 Emergency power. Emergency power shall be provided for the following loads:
SECTION 1203.2.21 IS ADDED TO READ AS FOLLOWS:
1203.2.21 Group I-1 and I-2. In addition to other provisions in this code, secondary power shall be provided for Group I-1 assisted living facilities and Group I-2 nursing homes to provide power for simultaneous operation of the following:
The secondary power supply (ies) can be a permanent on-site emergency or standby generator, fuel cell, or a mobile power supply(ies) were approved by the fire code official. Where the secondary power source is not a permanent on-site system, the facility shall submit a plan to the
fire code official detailing how secondary power will be provided. The secondary power supply plan shall become a component in the fire and life safety plan for the facility. Where the secondary power source is a mobile power supply located off-site and operated under contract to be delivered to the facility at times of need, the secondary power supply shall be capable of being delivered, connected and providing power within a 3-hour time frame following the loss of power.
SECTION 1207.11 IS AMENDED TO READ AS FOLLOWS:
1207.11.1 Equipment listings. ESS shall be listed and labeled in accordance with UL 9540 and marked “For use in residential dwelling units”. ESS listed and labeled solely for utility or commercial use shall not be used for residential applications.
SECTION 2003.8 IS ADDED TO READ AS FOLLOWS:
2003.8 Battery powered aviation ground support equipment. Lithium battery-powered aviation ground support equipment shall be listed and labeled in accordance with CAN/UL 5840 and shall be operated and maintained in accordance with the listing and manufacturer’s instructions.
SECTION 2808.1 IS AMENDED TO READ AS FOLLOWS:
2808.1 General. The storage and processing of wood chips, hogged materials, fines, compost, solid biomass feedstock and raw product produced from yard waste, debris and agro-industrial and recycling facilities shall comply with Sections 2808.2 through 2808.14.
SECTION 2808.10 IS AMENDED TO READ AS FOLLOWS:
2808.10 Emergency plan. The owner or operator shall develop a plan for monitoring, controlling and extinguishing spot fires and submit the plan to the fire code official for review and approval, and distributed to the responding fire department for response planning. This plan shall include a site map showing all buildings, major storage, processing and transfer areas, access roads and fire protection features including fire lanes.
SECTIONS 2808.11, 2808.12, 2808.13 AND 2808.14 ARE ADDED TO READ AS FOLLOWS:
2808.11 Fire Protection. Firefighting water supplies and application accessories must be present and accessible, the required amount and location to be approved by acceptance of the fire prevention plan. Examples of certain firefighting capabilities are:
2808.12 Site identification. Facility name and address shall be posted at main entrance and clearly visible from the street. Phone numbers for 24-hour emergency contacts shall be posted at the main entrance and clearly visible from the street.
2808.13. Site Security. Public access shall be limited with fences in place and approved “No Trespassing” signs. Entry gates shall be a minimum 14 feet wide and have sufficient turning radius for fire department access.
2808.14 Fire Prevention. A fire safety plan shall be submitted for approval, and it shall describe routine fire prevention procedures, including no smoking or open flames outside designated areas, fire watch with extinguishers during hot work, and separation of combustible materials from sources of ignition.
SECTIONS 3105.6.1 AND 3105.6.2 ARE AMENDED TO READ AS FOLLOWS:
3105.6.1 Independent inspector. The owner of a temporary special event structure shall provide an as-built certificate from the design professional or employ a qualified, independent approved agency or individual to inspect the installation of a temporary special event structure.
3105.6.2 Inspection report. If the owner employs an inspecting agency or individual, the owner shall furnish an inspection report to the fire code official. The inspection report shall indicate that the temporary special event structure was inspected and was or was not installed in accordance with the approved construction documents. Discrepancies shall be brought to the immediate attention of the installer for correction. Where any discrepancy is not corrected, it shall be brought to the attention of the fire code official and the designated responsible party.
SECTION 5001.1 EXCEPTION 7 IS AMENDED TO READ AS FOLLOWS:
7. Energy storage systems regulated by section 1207.
SECTION 5001.1 EXCEPTION 18 IS ADDED TO READ AS FOLLOWS:
18. Storage of battery types defined in Section 202 and complying with Section 322.
SECTION 5001.1 EXCEPTION 7 IS AMENDED TO READ AS FOLLOWS:
5001.7 Required specialized engineered plans. Group H occupancies shall be designed with the assistance of an engineer specializing in fire protection, licensed in the State of Texas.
SECTION 5001.1 EXCEPTION 7 IS AMENDED TO READ AS FOLLOWS:
7. Energy storage systems regulated by section 1207.
SECTION 5001.1 EXCEPTION 18 IS ADDED TO READ AS FOLLOWS:
18. Storage of battery types defined in Section 202 and complying with Section 322.
SECTION 5001.1 EXCEPTION 7 IS AMENDED TO READ AS FOLLOWS:
5001.7 Required specialized engineered plans. Group H occupancies shall be designed with the assistance of an engineer specializing in fire protection, licensed in the State of Texas.
SECTIONS 5601.2.4.2, 5603.3, Table 5604.5.2(3), 5608.3, and 5609.1 are amended to read as follows and Sections 5609.2 – 5609.5 have been added to read as follows:
5601.2.4.2 Fireworks display. The permit holder shall furnish a bond or certificate of insurance in an amount deemed adequate by the fire code official for the payment of all potential damages to a person or persons or to property by reason of the permitted display, and arising from any acts of the permit holder, the agent, employees or subcontractors. In accordance with the Texas Occupation Code, the applicant for any display shall submit evidence of a general liability insurance policy in the amount of $1 million.
5603.3 Loss, theft or unauthorized removal. The loss, theft or unauthorized removal of explosive materials from a magazine or permitted facility shall be reported to the fire code official, local law enforcement authorities and the U.S. Department of Treasury, Bureau of Alcohol, Tobacco, Firearms and Explosives within 24 hours.
Exception: Loss of Division 1.4G (consumer fireworks) need not be reported to the Bureau of Alcohol, Tobacco, Firearms and Explosives but shall be reported to the fire code official.
TABLE 5604.5.2(3)
TABLE OF DISTANCES (Q-D) FOR BUILDINGS AND MAGAZINES CONTAINING EXPLOSIVES—DIVISION 1.4c
|
QUANTITY OF DIVISION 1.4 EXPLOSIVES (NET EXPLOSIVES WEIGHT) |
DISTANCE IN FEET |
||||
|
Pounds over |
Pounds not over |
Inhabited Building Distance (IBD) |
Distance to Public Traffic Route (PTR) |
Intermagazine Distance a,b (IMD) |
Intraline Distance (ILD) or Intraplant Distancea (IPD) |
|
50 |
Not Limited | 50 | 50 | 50 |
50 |
For SI: 1 foot = 304.8 mm, 1 pound = 0.454 kg.
a. A separation distance of 100 feet is required for buildings of other than Type I or Type II construction as defined in the
International Building Code.
b. For earth-covered magazines, specific separation is not required.
1. Earth cover material used for magazines shall be relatively cohesive. Solid or wet clay and similar types of soil are too cohesive and shall not be used. Soil shall be free from unsanitary organic matter, trash, debris and stones heavier than 10 pounds or larger than 6 inches in diameter. Compaction and surface preparation shall be provided, as necessary, to maintain structural integrity and avoid erosion. Where cohesive material cannot be used, as in sandy soil, the earth cover over magazines shall be finished with a suitable material to ensure structural integrity.
2. The earth fill or earth cover between earth-covered magazines shall be either solid or sloped, in accordance with the requirements of other construction features, but not less than 2 feet of earth cover shall be maintained over the top of each magazine. To reduce erosion and facilitate maintenance operations, the cover shall have a slope of 2 horizontal to 1 vertical.
c. Restricted to articles, including articles packaged for shipment, that are not regulated as an explosive under Bureau of Alcohol, Tobacco, Firearms and Explosives regulations, or unpacked articles used in process operations that do not propagate a detonation or deflagration between articles.
5604.5.2.3 Fireworks 1.4G. Where magazines containing 1.4g fireworks cannot meet the 50’ separation inter-magazine distance, only 2 magazines will be allowed on same property.
5608.3 Approved fireworks displays. Approved fireworks displays shall include only the approved fireworks 1.3G, fireworks 1.4G, fireworks 1.4S and pyrotechnic articles 1.4G, which shall be handled by an approved, competent operator licensed by the State of Texas. The approved fireworks shall be arranged, located, discharged and fired in a manner that will not pose a hazard to property or endanger any person.
5609.1 General. The sale, storage, and display of Fireworks 1.4G is subject to the authority of the fire code official, including the authority to inspect, determine the presence of fire hazards.
5609.1.1 Applicability. This Section 5609 provides standards for the design and construction of buildings in which Fireworks 1.4G are to be stored, sold, or displayed. Such design and construction shall comply with this section and the Texas Fireworks Rules, current edition, as promulgated by the Texas State County Fire Marshal.
5609.1.2 Compliance with Fire Code. All structures used for the storage or sale of consumer fireworks 1.4G shall comply with the applicable provisions of the Harris County Fire Code for new structures, and with applicable sections of this sub-section.
5609.1.3 Fire Code Permit and Inspections. Any structure that is erected, occupied, or moved into or within the jurisdiction is considered new construction and requires a Fire Code permit and an inspection to ensure compliance with the adopted code.
5609.2 Definitions.
5609.2.1 Temporary Structure. Any structure that is erected, occupied, or moved into or within the jurisdiction, for a period of less than 180 days.
5609.2.2 Permanent Structure. Any structure that is erected, or moved into or within the
jurisdiction, for a period of more than 180 days.
5609.2.3 Fireworks Control Area. Spaces within a building where quantities of fireworks 1.4G, not exceeding the maximum allowable quantities, are stored, dispensed, used or handled.
5609.3 Conflict between provisions. If there is a conflict between the provisions of this section and the Fireworks Rules, the more stringent of the provisions shall apply.
5609.3.1 Limit of authority. This section does not limit the authority of the County Fire Marshal to inspect any retail site location or storage facility to require additional fire protection measures.
5609.4 Requirements for all retail sales, displays, and storage sites and facilities. All Fireworks 1.4G retail sales sites, storage buildings, and control areas, including temporary storage facilities such as trailers, semi-trailers, or metal shipping containers must conform to the minimum standards of this section.
5609.4.1 Physical Address and Emergency Contact. All retail sales sites and storage facilities must have the physical address and a 24-hour emergency contact number prominently posted on the outside of each site, close to the main entrance, in numbers at least 4 inches in height and ½ inch stroke in width on a contrasting background, and visible from the street or road fronting the property.
5609.4.2 Residential Storage. Fireworks 1.4G retail storage buildings shall not be used for residential occupancies. Use of a residential building for the storage of fireworks in excess of 125 pounds of pyrotechnic material shall be considered a change in occupancy.
5609.4.3 Maximum allowable quantity. No more than 125 pounds of pyrotechnic material may be stored and/or displayed in any control area. In the absence of documentation approved by the fire code official, 25 percent of the gross weight of the fireworks, including all packaging, will be used to determine the 125-pound limitation.
Exception:
1. The maximum allowable quantities can be increased 100 percent if the building is
equipped throughout with an automatic sprinkler system in accordance with Section 903.
2. The maximum allowable quantities may be greater than allowed by this section, subject
to approval by the County Fire Marshal, if the building meets all requirements for a Group H-
3 occupancy and Section 5609.4.
The aggregate quantity in use and storage shall not exceed the quantity listed for storage in the
Application for Permit.
5609.4.4 Minimum separation distances. Except as specified elsewhere in this section, structures shall be located in accordance with the requirements of Table 5609.4.1
Exceptions:
1. Trailers, semi-trailers, and metal containers used for storage only must be separated by
at least 50 ft. from any building or structure other than other trailers, semitrailers, or metal
shipping containers. There is no minimum distance between multiple trailers or semi-trailers
when used for storage only.
2. Permanent facilities permitted before January 1, 2019, may be separated from adjacent
buildings by less than 20 ft. if they are separated by a wall with a 1-hour fire resistance rating,
provided existing facilities are not enlarged or expanded.
3. Where multiple firework retail stands are on a single property, separation shall be no less
than 10 ft. Firework retail stands can be joined together with no separation if stands do not
exceed 70 ft. in length.
Table 5609.4.1 Minimum Separation Distances of Fireworks 1.4G Retail Sales Buildings, including Trailers, Semi-trailers, and Metal Shipping Containers
|
Type of Structure |
Minimum Distance |
|
From other trailers or semi-trailers |
0 ft. |
|
From Vehicles |
10 ft. |
|
From other buildings |
20 ft. |
|
From combustibles |
30 ft. |
|
From cooking equipment of any type, or any open flame equipment |
50 ft. |
|
Motor vehicles fuel-dispensing station dispensers or Retail propane dispensing station dispenser |
100 ft. |
5609.4.5 Electrical Work. Electrical work performed must be installed in accordance with the National Electrical Code.
5609.4.5.1 Required Listing. All electrical equipment, battery-powered equipment, and electrical cords shall be listed and shall be used in accordance with their listing.
5609.4.5.2 Temporary Power. The fire code official is authorized to give permission to temporarily supply and use power for up to 180 days. All temporary conductors shall comply with the National Electrical Code.
5609.4.5.3 Light fixture guards. All incandescent light fixtures within 25 ft. of any consumer fireworks shall have metal or plastic guards. All fluorescent light fixtures within 25 ft. of any consumer fireworks shall have plastic tube guards with caps or metal guards or plastic lens covers.
5609.4.5.4 Portable generators. Portable generators supplying power to consumer fireworks retail sales facilities shall comply with this section.
5609.4.5.4.1 Location distance. Portable generators shall be located not less than 10 ft. from the consumer fireworks retail sales facility and in an area free from grass, trash, and other combustible flammable materials.
5609.4.5.4.2 Surplus fuel. Generator fuel shall be stored in an approved safety container at least 10 ft. from the consumer fireworks retail sales facility. Fuel quantity shall be limited to not more than 10 gal.
5609.4.5.4.3 Extinguisher. For all generators a minimum 6 B.C. fire extinguisher shall be provided within 75 feet travel distance from generator location.
5609.4.6 Means of Egress. Means of egress including, but not limited to aisles, doors, and exit discharge, shall be clear at all times when the facility or the building is occupied.
5609.4.6.1 Number of exits. Each retail fireworks stand less than 16 feet in length shall have at least one walk door which opens outward, in a location approved by the fire code official. Stands measuring 16 feet or longer must have at least two walk doors which open outward, in locations approved by the fire code official.
5609.4.6.2 Maximum travel distance. Exits provided for all fireworks retail sales stands shall be arranged so that the maximum egress travel distance does not exceed 35 ft.
5609.4.6.3 Exit door requirements. The minimum dimensions of any walk door are 28 inches wide X 72 inches high. Walk doors must not be locked from the outside when the stand is occupied and must be immediately accessible from the inside.
5609.4.6.4 Minimum aisle width. A minimum distance of six feet shall be maintained from the front of the customer counter to the back side of the stand. The minimum clear exit aisle width is 28 inches.
5609.4.7 Fire Protection. All Fireworks 1.4G retail stands must comply with this section.
5609.4.7.1 Smoke detectors. Each stand will have an operational smoke detector in each sales area. If sleeping or rest areas are provided in the stand, there must be one smoke detector in each sales area and one in each sleeping or rest area.
5609.4.7.2 Cooking equipment. Cooking equipment of any type, or any open-flame equipment, shall not be permitted within 50 ft. of all stands, trailers, or shipping containers used for the storage or sale of consumer fireworks.
5609.4.7.3 Retail stand fireworks control areas. In Fireworks 1.4G retail stands, a flame break approved by the fire code official, may be installed every 8-10 feet to establish retail stand fireworks control areas. No more than 125 lbs. of pyrotechnic material may be stored and/or displayed in any retail stand fireworks control area.
5609.4.7.4 Approved flame break. An approved flame break, of not less than 3/4-inch plywood, shall be used to separate retail stand fireworks control areas. Separation shall begin at the back wall and extend to the furthest shelf point, and from the floor to the underside of roof. Fire caulking shall be applied at all penetrations and adjoining points along the 3/4-inch plywood separation.
5609.5 Specific requirements for retail fireworks sites other than stands. All indoor retail fireworks sites and storage facilities, other than stands, shall comply with the requirements of this section.
5609.5.1 Building Design. The retail fireworks sales building shall be a free standing, durable structure with no basement, and only one story of space accessible to the public.
5609.5.2 Multi-use building prohibited. The fireworks sales area shall not be part of a multi-use or multi-tenant building, except that office areas and restrooms ancillary to the building are allowed if:
1. Offices and related spaces are separated from fireworks storage or sales areas by fire barriers having a fire resistance rating of not less than 1 hour; and
2. Window openings in the fire barrier wall are protected by self-closing fire doors or fixed fire windows having a fire protection rating of not less than ¾ hour, and installed in accordance with NFPA 80, Standard for Fire Doors and Fire Windows.
5609.5.3 Assembly and educational occupancies prohibited. Assembly or educational occupancies cannot be used for the storage or sale of fireworks 1.4G.
5609.5.4 Application, Plans, Approval, Permits. All newly constructed firework retail sites other than stands shall comply with the adopted Harris County Fire Code Regulation and all processes shall be followed for plan submittal, approval, permitting, and inspection.
5609.5.5 Emergency response plan. The operator of each indoor retail sales site or storage facility shall prepare a written emergency response plan in accordance with Chapter 4 of this Code. The evacuation plan shall be posted in a conspicuous location that is accessible to the public as well as to persons employed or otherwise working in the facility.
5609.5.6 Maximum occupant load. The approved maximum occupant load shall be conspicuously posted near the main entrance using a format approved by the fire code official. Records of occupant load will be maintained onsite and available for inspection by the fire code official.
5609.5.7 Means of Egress. All means of egress in consumer fireworks retail sales facilities, other than stands, shall comply with the applicable requirements of this section.
5609.5.7.1 Minimum number of exits. The minimum number of exits provided from the retail sales area shall be not less than three, or more as determined in accordance with this Code.
5609.5.7.2 Maximum travel distance. Exits provided for the retail sales area of consumer fireworks retail sales facilities, other than stands, shall be located so that the maximum egress travel distance, measured from the most remote point to an exit along the natural and unobstructed path of egress travel, does not exceed 75 ft.
5609.5.7.3 Minimum aisle width. Aisles shall have a minimum clear width of 48 inches. Aisles and exit doors shall be kept free of any obstruction.
5609.5.7.4 Minimum exit door width. The minimum egress door width shall be not less than 36 inches in width and will provide a minimum clear opening width of 32 inches.
5609.5.7.5 Egress door swing. Unless approved by the County Fire Marshal, all egress doors shall be of the side- hinge swinging type and shall be arranged to swing in the direction of egress travel.
5609.5.7.6 Panic Hardware. Every egress door that has a latching device shall be provided with approved panic hardware.
5609.5.7.7 Roll-up or lift doors. Roll-up or lift doors may be used as egress doors when there is a readily distinguishable device that secures each door in the open position whenever the building is occupied.
5609.5.8 Sales area design. Fireworks sales display areas shall be sufficiently designed to prevent customers from handling fireworks, unless an attendant is directly assisting the customer.
5609.5.8.1 Visual Supervision. The sales area shall be designed and constructed so that fireworks shall be under the visual supervision of a store employee or other responsible party while the store is open to the public.
5609.5.8.2 Height counter and displays. Partitions, counters, shelving, cases, displays, product and similar sales areas shall not exceed 6 ft. in height above the floor surface inside the perimeter of the retail sales area.
5609.5.8.3 Height perimeter. Where located along the perimeter of the retail sales area, the maximum height of sales displays, shelving, and product shall be limited to 12 ft.
5609.5.9 Fire protection.
5609.5.9.1 Fire Extinguishers. Portable fire extinguishers shall be specified as required for extra (high) hazard occupancy in accordance with NFPA 10, Standard for Portable Fire Extinguishers.
5609.5.9.1.1 Number and Placement. Every indoor retail sales building shall have not less than two portable fire extinguishers with a minimum 2A rating. At least one approved Class A fire extinguisher shall be provided for each 1,000 square feet of floor space, not to exceed 75 ft. travel distance.
5609.5.9.2 Fire alarm system. A fire alarm system, installed in accordance with NFPA 72, shall be required in all consumer fireworks retail sales facilities. Facilities less than 3,000 sq. ft. in area AND in existence and continuously permitted before January 1, 2005, are exempt from compliance provided such facilities are not enlarged or expanded beyond their January 1, 2005 operation.
5609.5.9.3 Automatic fire sprinklers. An automatic sprinkler system shall be required in all consumer fireworks retail sales facilities. Facilities less than 6,000 sq. ft. in area AND in existence and continuously permitted before January 1, 2005 are exempt from compliance, provided such facilities are not enlarged or expanded beyond their January 1, 2005 operation.
5609.5.9.4 Smoke Control. All sites must have a minimum average ceiling height of 12 ft. Smoke and heat vents designed and installed in accordance with NFPA 204, Standard for Smoke and Heat Venting shall be provided in consumer fireworks storage buildings. Facilities less than 50,000 sq. ft. in area and in existence and continuously permitted before January 1, 2005, are exempt from compliance, provided such facilities are not enlarged or expanded beyond their January 1, 2005 operation.
5609.5.10 Other codes, standards, and laws. Unless specifically outlined in this chapter, all retail fireworks sites shall comply with the other applicable chapters of this code, the Texas Occupations Code 2154, Texas Local Government Code 352, and the Texas Fireworks Rules.
SECTION 5809 IS ADDEDTO READ AS FOLLOWS:
SECTION 5809
ON-DEMAND HYDROGEN MOBILE FUELING OPERATIONS
5809.1 General. On-demand hydrogen mobile fueling operations that dispense gaseous hydrogen into the fuel tanks of motor vehicles shall comply with Sections 5809.1 through 5809.6.5.
5809.1.1 Approval required. Hydrogen mobile fueling operations shall not be conducted without first obtaining a permit and approval from the fire code official. Hydrogen mobile fueling operations shall occur only at approved locations. The fire code official is authorized to approve individual locations or geographic areas where mobile fueling is allowed.
5809.2 Hydrogen mobile fueling vehicle or trailer. An on-demand hydrogen mobile fueling vehicle or mobile fueling trailer shall be that which is utilized in on-demand fueling operations for the dispensing of gaseous hydrogen into the fuel tanks of motor vehicles.
5809.2.1 Hydrogen mobile fueling vehicle requirements. Each hydrogen mobile fueling vehicle or mobile fueling trailer shall comply with all local, state and federal requirements, as well as the following:
5809.3 Required documents. Documents developed to comply with Sections 5809.3.1 through 5809.3.3 shall be updated as necessary by the owner of the mobile fueling operation and shall be maintained in compliance with Section 110.3.
5809.3.1 Safety and emergency response plan. Hydrogen mobile fueling operators shall have an approved written safety and emergency response plan that establishes policies and procedures for fire safety, release and control, personnel training and compliance with other applicable requirements of this code.
5809.3.2 Training records. Hydrogen mobile fueling vehicles or mobile fueling trailers shall be operated only by designated personnel who are trained on proper fueling procedures and the safety and emergency response plan. Training records of operators shall be maintained.
5809.3.3 Site plan. Where required by the fire code official, a site plan shall be developed for each location at which hydrogen mobile fueling occurs. The site plan shall be of sufficient detail to indicate the following:
5809.4 Hydrogen mobile fueling areas. Hydrogen mobile fueling shall not occur on public streets, in public ways or inside buildings. Fueling on the roof level of parking structures or other buildings is prohibited unless access to the roof level is available without entering the structure or building.
5809.4.1 Separation. The point of connection of the vehicle being fueled shall not take place within the distances specified by NFPA 2 Table 7.2.2.3.2 based on the maximum rated capacity of the hydrogen mobile fueling vehicle.
5809.4.2 Sources of ignition. Smoking, open flames and other sources of ignition shall be prohibited within 25 feet (7620 mm) of fuel-dispensing activities. Signs prohibiting smoking or open flames within 25 feet (7620 mm) of the vehicle or the point of fueling shall be prominently posted on the hydrogen mobile fueling vehicle. The fuel cell of vehicles being fueled shall be shut off during fueling.
5809.5 Equipment. Hydrogen mobile fueling equipment shall comply with Sections 5809.5.1 and 5809.5.2.
5809.5.1 Dispensing hoses, nozzles and equipment. Dispensing hoses, nozzles and equipment shall comply with NFPA 2.
5809.5.2 Fire extinguisher. An approved portable fire extinguisher complying with Section 906 with a minimum rating of 4-A:80-B:C shall be provided on the hydrogen mobile fueling vehicle with signage clearly indicating its location.
5809.6 Operations. Hydrogen mobile fueling vehicles or mobile fueling trailers shall be operated in accordance with this section and NFPA 2.
5809.6.1 Attendant. Hydrogen mobile fueling vehicles or mobile fueling trailers shall be attended at all times during fueling operations, with brakes set and warning lights in operation.
5809.6.2 Emergency access roads. Hydrogen mobile fueling vehicles shall not obstruct emergency vehicle access roads.
5809.6.3 Dispensing hose. Where equipped, hydrogen mobile fueling vehicles or mobile fueling trailers shall be positioned in a manner to preclude traffic from driving over the dispensing hose. The dispensing hose shall be properly placed on an approved reel or in an approved compartment prior to moving the mobile fueling vehicle.
5809.6.4 Safety cones. Safety cones or other visual barriers shall be employed as warning devices to highlight the vehicle fueling area.
5809.6.5 Vehicle lights. The hydrogen mobile fueling vehicle or mobile fueling trailer flasher lights shall be in operation while dispensing operations are in progress.
5809.6.6 Nighttime deliveries. Nighttime deliveries shall be made only in areas deemed adequately lighted by the fire code official.
5809.6.7 Spill reporting. Releases shall be reported where required by Section 5003.3.1.
THE USER NOTE TO CHAPTER 80 IS AMENDED TO READ AS FOLLOWS:
About this chapter: This code contains numerous references to standards promulgated by other organizations that are used to provide requirements for materials and methods of construction. This chapter contains a comprehensive list of all standards that are referenced in this code. These standards, in essence, are part of this code to the extent of the reference to the standard.
This chapter lists the standards that are referenced in various sections of this document. The standards are listed herein by the promulgating agency of the standard, the standard identification, effective date and title, and the section or sections of this document that reference the standard. If the State of Texas has adopted any of the listed standards, the more stringent or more current standard of the provisions shall apply.
CHAPTER 80 is amended to add the following reference standards:
NFPA
NFPA 1, Uniform Fire Code—Current State adopted edition, Section 20.5
NFPA 101® Life Safety Code®— Current State adopted edition, Chapter 33
Email: FMOSupport@fmo.hctx.net
Phone: (713) 274-1700
Fax: (281) 436-8005
Our offices no longer offer walk-in services. Please call to schedule office visits.